DATASHEET AES ST32

Table Of Contents
Typ: article:
AES-ST3.2 Ventilation & Smoke Extraction Control Unit
AES-BT1S Operating & display module for 1-stage fan
AES-BT2S Operating & display module for 2-stage fan
AET-1 AP panel, 1-stage, "Ventilation" (remote switch)
AET-2 AP panel, 2-stage, "Ventilation" (remote switch)
FWS-S4 Fire brigade switch „smoke extraction“ with
4 indicator lights and standard-key-switch
FWS-P4 Fire brigade switch „smoke extraction“ with
4 indicator lights and mounting for DIN profile cylinder
FWS-ZY DIN profile cylinder-key set for fire brigade switch
ARM-1 Automatic smoke alarm with alarm socket
AMM-2 Automatic multi-sensor alarm, optical / thermal with alarm socket
HRM-3K-[ ] Smoke vent button „smoke exhaust" in plastic housing
HRM-3M-[ ] Smoke vent button „smoke exhaust" in metal housing
calour grey [GR] / yellow [GE] / orange [OR]
DK-GLAS Spare glass pane for pushbutton alarm
Order-Code
Technical data
Terminal voltage control V AC 230
Smoke extraction flap:
Rated voltage / rated current V AC / A 230 / 2
Control fuse (-F1) A 2 medium slow
Control - low voltage V DC 24
Control fuse 24VDC (-F2) mA 400 medium slow
max. Connection power 24V DC (on terminal 17:18 / ext. panel )
P = 10W - 0,35W x (quantity HRM + quantity FWS)
Contacts floating signal V AC / A 230 / 2
Detector loops (FWS, BMZ, ARM, HRM):
Rated voltage V DC 22
max. quantity of detectors per loop see wiring diagram
max. cable length per loop m 450
recommended signal conductor Art solid, 0,8mm
terminating resistor kOhm 10
trip resistance kOhm 1
wire breakage detection mA <1
short-circuit (short-circuit proof) mA > 40
Evaluation motor protection (PTC)
Ok + (reset about button) kOhm < 1,9
release kOhm > 2,7
current load Analog output mA max. 10
provided by customer repair switch: only with load disconnect!
ambient temperature °C 0 to +40
dimensions l/w/d mm 150/97/65
identification CE
applied standards EN 12101-9 , DIN 18232-5/6
EMC tested to EN 50130-4 , EN 55011
Connection diagram
AES-ST3.2
AES-BT1S4 /
AES-BT2S4
Entrauchung
Überlast
Betrieb
Bereit
ABLUFT/ENTRAUCHUNG
Bereit
Entrauch. Stufe 1
Stufe 2
BMZ
-
2x2x0,8mm²
-W5
smoke extraction
flap
5x1,5mm²
-W10
auto. smoke alarm
ARM-1 / AMM-2
2x2x0,8mm²
-W7
manual smoke vent button
HRM-3K / HRM-3M
4x2x0,8mm²
-W8
M
1~
PE
Z A N
PE
PE PE
Auf
Zu
5
7 8 4 3 2
BMZ
Rep.
1
1
1
1
2
2
2
max. Anzahl: 20 max. Anzahl: 20
1
2
Resistor or bridge removed when device or detector connected.
Resistor on the last or insert single detector in the loop.
Repair switch
-
2x2x0,8mm²
-W9
10kW
10kW
10kW
10kW
1
10kW
10kW
Specified line types and dimensions are minimum
requirements excluding laying, cable length,
type of network and necessary integrity.
The related to the building specifications
must be taken autonomously by the plumber.
Function retaning line
motor protection
Control
230VAC
40 41 42 N
L
L
27 28
N
Open
Close
L
F1
2322
automatic
smoke alarm
Enable
ventilation
Fire brigade switch
1 32
7654
ext. panel
12 13
triggered
decpicted
50 51 52
Smoke extraction
signal
floating
br
DL-plug
14 pol.
ge
max. contact load
230V AC / 6A
53 54 55
Error
signal
floating
AES-ST3.2
19 20 15 1614
3029
10 11
17 18
24VDC
BMZ
8
9
+
-
or
TK or MSRPTC
L01
With compact controller AES-D/-DA/-SD/-SS/-W or
if installed in control cabinet, factory pre-wired.
manual smoke vent button
Rep.-switch
MT 2A
24V/15VA
N
MT 0,4A
F2
-
+
31 32
Look
Fail
Reday
Smoke Extraktion
Control off
(FWS-Off / look)
signal
DKM
DKT
ON
BMZ autoRST
10V
stage 2
smoke ext.
25 26
U = 0-5V
U = 5-10V
U = stage 2 / 10V
I max. 10mA
Y
FU /
EC-Motor
Y
Y
stage 1:
stage 2:
smoke ext.:
stage 2stage 1
OnBoard-Diagnose
reset
System
reset
Ribbon cable
to front module
24
+24VDC
Lamp test
1
2 3 7 86
Fire brigade switch
FWS-P4 / FWS-S4
4x2x0,8mm²
-W4
2 3 6 7 81
10kW
1kW1kW
1kW
1kW1kW
1kW
2
max. Anzahl: 6
ge gn rt
2 3 6 7 81
ge gn rt
Feedback
flap „open“
3x1,5mm²
-W11
St.1 St.2
smoke
extraction
N
N 45 46
43 44
Enable
ventilation
St.1N St.2
with 1-stage
fan!
Panel ventilation
AET-1 / AET-2
4x2x0,8mm²
-W6
0-1-2
St.1 Störung
1 2 3 4 5
St.2
10kW
Connection standard for flap with 3-point control!
Connect „OPEN“ only if no spring return is installed
for this flap position!
Connect “L” terminal 40 for flap with 2-point control!
„Enable ventilation“ contact opens when the flap is OPEN
- - -
60
61
press button:
direct : DKM, BMZ
> 1sec: RM
> 3sec: FWS
+
+
-
9
rt
9
9
rt
5 76 4
21
8 3 2 1
5 76 48 3 2 1
11.15
D
Edition Version
www.systemair.de