Data sheet 3~ R DKKTG[1]
TIL03_18 (27.11.07) Subject to technical modifications!
9.
9.3.2-GB
Transformer based controller for 3~ motors
5-step controller inclusive integral thermistor releasing unit
Type: R-DK...KT(G)
Examples of applications for controlling 3~ fans in 5-steps
Manual 5-step speed change-over of one or more 3~ fans e. g. in:
heat exchangers (as warm-air heaters), hoods, ventilation of rooms.
An integral thermistor releasing unit type U-EK230E with ATEX-approval can be used for the temperature monitoring
of motors in explosion protected range. Six thermistors (DIN 44081 or DIN 44082) can be connected in series.
According to the type of motor at least two or three single sensors are installed. Fans used in explosion protected
range must have three single sensors. That means at most two motors of this type can be connected.
The device includes potential-free and 230 V power on contacts for the connection of damper control motors or gas
valves (hoods application) (see on back).
Equipment Enclosed version IP21 / 54
Transformer based controllers for voltage controllable 3~ fans
•
5-step switch for manual speed control
•
Remote control (ON/OFF) via potential-free contact
(terminals „RT”-„RT”).
• Motor protection using thermistor connection (terminals „T1"-„T2").
If one of the thermistor is released, the unit switches off and not
on again. Restart after cooling the drive unit by switch-off and after that
switch on the mains voltage or by step-switch („reset").
•
A power on lamp is integrated.
• Automatic switch on after power failure.
• Additional power on contact
- Potential-free changer
- 230 V switched and constant voltage
Technical data
- Line voltage 3~ 400 V, 50/60 Hz
- Output voltage 95 V - 145 V - 190 V - 240 V - 400 V
- Max. load of the power on contacts
⋅ Potential-free changer (terminals 1, 2, 3) 250 V AC / 2 A
⋅ 230 V switched and constant voltage max. 1 A
(terminals N↓, L↓, )
- Max. ambient temperature +40° C
- Housing top consists of plastic,
colour light grey,
bottom aluminium die casting
Type Part-No. Rated current Max. line fuse Max. heat dissipation approx. Protection class Weight
R-DK3KTG 302567 3 A 6 A 60 W IP54 13.0 kg
R-DK4KT 302568 4 A 8 A 75 W IP21 13.0 kg
R-DK5.2KTG 302569 5.2 A 13 A 80 W IP54 18.5 kg
R-DK7KT 302570 7 A 16 A 110 W IP21 18.5 kg
Dimension sheet [mm] Connection diagram
R-DK...KT(G)
N L1 L2 L3
L3NL2L1PE
Netz / Line / Secteur
Nätanslutning
3 ~ 400 V 50/60 Hz
U V W11 1412 RT
01
SR171K13
27.11.2007
L L N
230 V AC
Kontaktbelastung
Contact rating
Pouvoir de coupure
Kontaktbelastning
RT
1* Wenn Funktion nicht benötigt wird, Klemmen brücken 1* Si la fonction n’est pas utile, les bornes doivent être reliées
If function is not needed, terminals must be bridged Om funktionen inte används, måste plintarna byglas
1*
Aus / Ein
Off / On
Arrêt / Marche
Av / På
250 V AC
max. 2 A
230 V AC
max. 1 A
T1T2
M
3 ~
TP
TP
3 ~ Motor
mit eingebauten Temperaturfühlern
with internal thermistors
avec thermistances intégrés
med utdragen termistorer
PE
VWU
Y/
Ziehl-Abegg AG
Heinz-Ziehl-Straße
D-74653 Künzelsau
Tel.: +49 (0) 7940 16-0
Fax: +49 (0) 7940 16-504
info@ziehl-abegg.de http://www.ziehl-abegg.de
L