Technical data
Supply voltage 230...400 (210 - 415 V ~ 50/60 Hz 16 A)
Pulse period 60 s
Mounting Wall
Power dissipation 20 W of heat at full load
Protection class IP20
P-band 20 K (rapid temperature changes), 1.5 K (slow temperature changes)
I-time 6 min (rapid temperature changes)
Ambient temperature 0...30 °C
Ambient humidity Max. 90 % RH, non-condensing
Storage temperature -40...+50 °C
Dimensions, external (WxHxD) 95 x 153 x 41 mm
Cable connection Cage clamp
Weight (incl. packaging) 0.33 kg
Output load Resistive load, max 16 A, min 1 A
Sensor inputs External main sensor and external sensor for temperature limitation
Sensor element NTC Regin standard
Setpoint range 0...30 °C (the external sensor determines the temperature range)
Setpoint alternatives Either internal setpoint potentiometer or external setting device
Night setback 0...10 K
Indication Red LED that is lit when power is pulsed to the heater
This product carries the CE-mark. More information is available at www.regincontrols.com.
Accessories
Article Description
PULSER- ADD Slave-controlled add-on unit for electric heating controller
TG-K3xx Duct sensor, NTC Regin
TG-G1xx Floor sensor, NTC Regin
TG-R4xx Room sensor, NTC Regin
TRY-RATT-2271 / -1588 / -1589 / -1590 Setpoint knobs and scales for different setpoint ranges
HEAD OFFICE SWEDEN
Phone: +46 31 720 02 00
Web: www.regincontrols.com