SAVE VTC 700 SERVICE AND ACCESSORIES INSTALLATIONV1
Table Of Contents
- 1 Overview
- 2 Important Safety Information
- 3 Configuration
- 4 Service
- 5 Accessories
Accessories
|
37
Note:
A duct temperature sensor can be connected to analog inputs 6–7 on the connection board for better
access and then configured as a supply air temperature sensor. However the internal supply air
temperature sensor must be disabled in the control panel first.
7. Water heater and its components are now configured.
5.3.4 Duct water cooler
A duct water cooler is supposed to be installed in supply air duct to provide a
cooled down air to the apartment.
• WC — water cooling battery
• SAT — supply air temperature sensor
• S — valve actuator
• 1 — Outdoor air
• 2 — Supply air
• 3 — Extract air
• 4 — Exhaust air
Component/product — Article number:
• CWK 250-3-2,5 Duct cooler,circ — 30024
• RVAZ4 24A Actuator 0-10V (S) — 9862
• ZTV 15-1,6 2-way valve — 9824
• ZTR 15-1,6 valve 3-way — 9673
• Duct sensor -30-70C (SAT) — 211524
• PSS48 Transformer 24V — 204385
Fig. 10 Duct cooler connections
Installation and connection
1. Install a duct water cooler in the duct. Connect pipes, 2/
3–way valve and actuator.
Important
Do NOT use 24V DC power output from the
connection board for valve actuator.
2. Connect actuator (S) to any free analog output.
3. An internal supply air temperature sensor (SAT, default connection AI2 on the main circuit board) must be replaced
by a duct temperature sensor which can be acquired as an accessory. A duct temperature sensor must be installed in
the duct after water cooler. Connect the duct temperature sensor to analog input 2 (AI2) replacing the internal supply
air temperature sensor.
Note:
A duct temperature sensor can be connected to analog inputs 6–7 on the connection board for better
access and then configured as a supply air temperature sensor. However the internal supply air
temperature sensor must be disabled in the control panel first.
Configuration
1. Go to Service menu
| v01