Accessories
|
35
5.3.2.3 Heater installed in the supply air duct (extra zone)
Installation and connection
1. Install an electric heater (ELH) at least 100 mm distance
from the unit in the supply air duct. A relay (RL) is used
to control the heater. Connect relay to any free digital
output on the connection board (CB).
2. Connect the power supply to the electric heater via a
relay. A circuit breaker (BRK) is not included in the
package and must be ordered separately. It must be in-
stalled in the circuit.
3. Install a temperature sensor (ECT) after the electric
heater and connect it to any free analog input on the
connection board (CB).
Supply air heater configuration
1. Go to Service menu
2. Enter password (default 1111)
3. Set the heater type: Components > Extra Controller > Extra Controller Mode > Heating.
4. Configure connection of the heater. Go to Service menu. Select Output menu. In next menu select DIGITAL tab.
Select the digital output to which the heater is connected. Example if it is connected to DO3 on the connection board,
then select DIGITAL OUTPUT 3 and select Step Controller Y4 Extra Controller from the output type list.
5. Configure the installed sensor. Go to menu Service > Input > ANALOG. Select the analog input to which the sensor
is connected. Example if it is connected to AI6 on the connection board, then select ANALOG INPUT 6 > Extra Con-
troller Temp. Sensor (ECT).
5.3.3 Duct water heater
A duct water heating battery is supposed to be installed in supply air duct.
• WH — water heating battery
• FPT — frost protection sensor
• SAT — supply air temperature sensor
• S — actuator for valve
• 1 — Outdoor air
• 2 — Supply air
• 3 — Extract air
• 4 — Exhaust air
Component/product — Article number:
• VBC 200-2 Water heating battery— 5459
VBC 200-3 Water heating battery — 9841
• VAZ4 24A Actuator 0-10V (S) — 9862
• ZTV 15-0,6 2-way valve — 6571
ZTV 15-1,0 2-way valve — 9823
ZTR 15-0,6 valve 3-way — 6573
ZTR 15-1,0 valve 3-way — 9672
• Duct sensor -30-70C (SAT) — 211524
• Surface sensor -30-150C (FPT) — 211523
• Transformer 24V — 202692