12
|
Maintenance
Fig. 4 Heat exchanger
Even if the required maintenance is carried out, dust will
build up in the exchanger block. It is therefore of vital im-
portance for the upkeep of a high efficiency that the ex-
changer block is removed from the unit and cleaned
periodically as described below. Clean the heat exchanger
at least every 3 years or when required.
1. Stop the unit by disconnecting the mains.
2. Open the front hatch. See chapter 4.2.
3. Pull out the exchanger using the strap at the front.
4. Gently vacuum the heat exchanger.
5. Remount the heat exchanger.
6. Close and lock the front hatch and connect the unit to
mains.
4.5 To clean fans
Danger
• Make sure that the mains supply to the unit is disconnected before performing any maintenance or
electrical work!
Warning
• Risk of injury due to rotating parts that have not come to a complete standstill after mains supply to the
unit have been disconnected.
Warning
• Beware of sharp edges during mounting and maintenance. Use protective gloves.
1 Disconnect the unit from the mains by pulling out the wall plug
2 Remove the cover plates
3 Disconnect the fan power cables. The cables are found beside the fans.
254297 | v01