SAVE VTC 200 SERVICE AND ACCESSORIES INSTALLATIONV1 1

36
|
Accessories
Configuration
1. Go to Service menu
2. Enter password (default 1111)
3. Activate the actuator. Go to Components menu, select Cooler menu and select type as Water. Choose actuator
voltage type. Do advanced settings if necessary.
4. Configure control signal to the actuator. Go to Service menu. Select Output menu. In next menu select ANALOG
tab. Select the analog output to which the control wire of the actuator is connected. Example if it is connected to AO3
on the connection board, then select ANALOG OUTPUT 3 and select Y3 Cooling from the output type list.
5. Since a duct temperature sensor replaces internal supply air temperature sensor, it doesn’t need to be re-configured.
Note:
A duct temperature sensor can be connected to analog inputs 6–7 on the connection board for better
access and then configured as a supply air temperature sensor. However the internal supply air
temperature sensor must be disabled in the control panel first.
6. Duct cooler and its components are now configured.
6.3.4 Ground heat exchanger
The ground heat exchanger can be connected to an outdoor air duct to heat the air and prevent the heat exchanger
from icing up, or to cool the air to reduce the need for cooling.
GHT Ground heat exchanger
ECT extra controller temperature sensor
OAT outdoor air duct temperature sensor
RL relay
1 Outdoor air
2 Supply air
3 Extract air
4 Exhaust air
| v1.1