SAVE VTR 100B INSTALLATIONV1

Table Of Contents
4
| Technical Data
3.2 Connections and Left/Right-hand orientation
Fig. 3 Left—hand and right-hand orientation
Position Description
R
Right-hand orientation (Outdoor air connection is situated on the right side of the unit
viewed from the front)
Default version at delivery.
L
Left-hand orientation (Outdoor air connection panel is situated on the left side of the unit
viewed from the front)
The unit can be switched to left-hand orientation by changing mounting bracket and
connection box location.
Symbol
Description
Symbol
Description
Symbol
Description
Supply air
Outdoor air Cooker hood air
Exhaust air
Extract air
Duct connections: Ø 125 mm
3.3 Installation recommendation regarding condensation
3.3.1 Condensation inside of the unit
When the unit is installed in a cold attic (close to outdoor temperature) the unit should run continuously. If the unit is in-
tended to be stopped by the user manually or due to calendar function we recommend to install air tight dampers at ex-
tract and supply air ducts. The dampers will ensure that no air circulates from the warm parts of the building through
the unit to outside (chimney effect). If no dampers are installed there is risk of condensation inside the unit and the out-
door ducts during these stop periods. It also might be that cold air from outside could pass the unit and enter into the
building. That could cause condensation outside the supply and extract air ducts and even at the valves in the rooms.
When the unit is not running due to late commissioning in winter time, the supply and extract air ducts should be dis-
connected and closed due to above mentioned effects until commissioning and regular operation.
254537 | v2