SAVE VSR 150B INSTALLATIONV01 20210316
Table Of Contents
Installation |
9
Follow the ventilation drawing when connecting the unit to the duct system.
6.1 Ventilation Duct Connection and Insulation
Important
• Always cover the ventilation ducts during construction period.
• Make sure there are no loose objects or impurities inside the ducts.
Install the ducts, supply air diffusers and air intake grilles as shown in the ventilation drawing.
• Supply air and extract air ducts must be insulated if located in cold places.
• Outdoor air and exhaust air ducts with cold air must be insulated if located in warm places (inside building’s vapour
barrier).
It is very important to insulate cold ducts and joints tightly without any gaps, otherwise there is a risk of condensation
which may result in moisture damage.
Do not install the ducts directly against structural building elements to avoid sound propagation. Use acoustic insulation
and sound attenuators.
254288 | v01