CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
 - About Corrigo
 - Display, buttons and LEDs
 - The menu system
- Navigating the menus
 - Running mode
 - Temperature
- Setpoint Supply air temperature control
 - Setpoint Outdoor temperature compensated Supply air control
 - Setpoint Cascaded room temperature control
 - Setpoint Cascaded extract air temperature control
 - Setpoint Outdoor compensated room temperature/extract air control
 - Support control heating/Support control cooling
 - Frost protection temperature
 - Exchanger de-icing
 - Heat exchanger efficiency monitoring
 - Recirculation
 - Extra controller unit
 - Enthalpy control
 
 - Air control
- Pressure control SAF (there are also corresponding menus for EAF)
 - Flow control SAF (there are also corresponding menus for EAF)
 - Manual frequency control SAF (there are also corresponding menus for EAF)
 - Frequency control external
 - Frequency control SAF with EAF slave/flow control (also available for opposite function)
 - CO2
 
 - Humidity control
 - Time settings
 - Access rights
 
 - Other functions
 - Index
 
Corrigo ventilation user guide, revision F  Other functions    
25 
Language 
If RIGHT is pressed three times when the start menu is shown, a menu is displayed in which 
the language can be changed.  
The different language files are stored in the application memory and are downloaded to the 
work memory. If a Corrigo has been reloaded with a program revision newer than the 
factory revision using E tool
©
, the controller will not allow language files to be downloaded 
from the application memory. This is because there is a risk that the language files are not 
compatible with the new revision. Therefore, you are limited to the two languages you have 
downloaded using E tool
©
. 
Indication LEDs 
Status indication can be found in the upper left corner of the controller. For controllers with 
display, the alarm indication and change mode LEDs are located in the keypad area. 
Status indication 
Changing the battery 
Corrigo has an internal battery to ensure the operation of the memory and real-time clock in 
the event of a power failure. 
When the alarm ”Internal Battery” is activated and the battery LED lights up red, the battery 
has become too weak and needs to be changed. Nonetheless, due to a backup capacitor, the 
controller will function at least 10 minutes without power supply.  
Since changing the battery requires knowledge of proper ESD protection, as well as 
dismantling and opening of the unit, this should be handled by skilled service personnel. 
Designation   Colour  Description 
Tx  Green  Port 1/2, transmitting 
Rx  Green  Port 1/2, receiving 
Serv (…Lon models)  Yellow  Service LED LON, commissioning 
LAN (…W models)  Yellow/Green  Green: Connected to other network 
equipment 
Blinking green: Network traffic 
Blinking yellow: For identifying 
P/B (Power/Battery)  Green/Red  Power on/Battery error 
Controllers with built-in display: 
 
Red  Alarm indication. Flashing: There are 
unacknowledged alarms. Fixed: There are 
alarms which have been acknowledged but 
where the fault remains. 
 
Yellow  Change mode. Flashing rapidly: The 
display contains changeable values. 
Flashing slowly: A password is needed to 
make changes in the display. 