CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
 - About Corrigo
 - Display, buttons and LEDs
 - The menu system
- Navigating the menus
 - Running mode
 - Temperature
- Setpoint Supply air temperature control
 - Setpoint Outdoor temperature compensated Supply air control
 - Setpoint Cascaded room temperature control
 - Setpoint Cascaded extract air temperature control
 - Setpoint Outdoor compensated room temperature/extract air control
 - Support control heating/Support control cooling
 - Frost protection temperature
 - Exchanger de-icing
 - Heat exchanger efficiency monitoring
 - Recirculation
 - Extra controller unit
 - Enthalpy control
 
 - Air control
- Pressure control SAF (there are also corresponding menus for EAF)
 - Flow control SAF (there are also corresponding menus for EAF)
 - Manual frequency control SAF (there are also corresponding menus for EAF)
 - Frequency control external
 - Frequency control SAF with EAF slave/flow control (also available for opposite function)
 - CO2
 
 - Humidity control
 - Time settings
 - Access rights
 
 - Other functions
 - Index
 
Corrigo ventilation user guide, revision F  The menu system    
15 
During recirculation, offset SAF makes it possible to add to the supply air fan an offset to 
the setpoint during normal operation. 
If pressure control has been configured, the offset is set in Pa. If flow control has been 
configured, it is set in m3/h. If manual control has been configured, the offset is set in %. 
If you have selected the Offset function, which is a deviation from the regular supply air 
setpoint, you will instead be given the option to change this offset value here. 
Extra controller unit 
An independent temperature control circuit for control of for 
example after-heaters. The circuit can be configured to either 
heating or cooling.  
Enthalpy control 
Enthalpy control is a function for overriding the mixing damper 
output signal to recirculation if the enthalpy is higher outdoors 
than indoors. 
  Submenu for reading of outdoor temperature and outdoor 
air humidity.  
Submenu for reading of indoor temperature and air 
humidity in the room. 
Shows if enthalpy control is active or not. 
Extra unit 
Actual: 21.2°C 
Setpoint: 20.0°C 
Enthalpy indoor: 
 35.5 kJ/kg 
Enthalpy outdoor: 
 36.4 kJ/kg 
Outd temp 
 Act: 19.2 °C 
Humidity outdoors 
Act: 51.1 % RH 
Indoor temp 
Act: 19.9°C 
Humidity indoors 
Act: 44.3 % RH 
Override cool  
recovery due to 
enthalpy: 
Active 