CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
 - About Corrigo
 - Display, buttons and LEDs
 - The menu system
- Navigating the menus
 - Running mode
 - Temperature
- Setpoint Supply air temperature control
 - Setpoint Outdoor temperature compensated Supply air control
 - Setpoint Cascaded room temperature control
 - Setpoint Cascaded extract air temperature control
 - Setpoint Outdoor compensated room temperature/extract air control
 - Support control heating/Support control cooling
 - Frost protection temperature
 - Exchanger de-icing
 - Heat exchanger efficiency monitoring
 - Recirculation
 - Extra controller unit
 - Enthalpy control
 
 - Air control
- Pressure control SAF (there are also corresponding menus for EAF)
 - Flow control SAF (there are also corresponding menus for EAF)
 - Manual frequency control SAF (there are also corresponding menus for EAF)
 - Frequency control external
 - Frequency control SAF with EAF slave/flow control (also available for opposite function)
 - CO2
 
 - Humidity control
 - Time settings
 - Access rights
 
 - Other functions
 - Index
 
The menu system   Corrigo ventilation user guide, revision F   
18 
Frequency control SAF with EAF slave/flow control (also available for 
opposite function) 
A pressure control where either the SAF or EAF is 
operated as a slave. This function is also available 
featuring flow control. 
Controller output 
comp if cooling 
 0 at R U S= 0 % 
100 at R U S= 0 % 
Controller output 
comp if heating 
 0 at R U S= 0 % 
100 at R U S= 0 % 
Controller output 
compensation 
Not active 
Compensation only 
when 
1/1-speed : No 
defrosting: No 
Pressure ctrl SAF 
Actual: 480 Pa 
 Setp.: 490 Pa 
Pressure ctrl SAF 
Setp 1/1: 500 Pa 
Setp 1/2: 250 Pa 
Outdoor comp output 
 -20 °C = 0 Pa 
 10 °C = 0 Pa 
Act comp: 0 Pa  
Comp sens:Roomtp.1 15  
°C = 0  Pa 
20 °C = 0 Pa 
25 °C = 0 Pa  