CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 6 Input Status Register  69 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
InputOutput.Exp2DigOut7 
L 
10182 
Digital 
outputs 
Value of DO7 Expansion unit 2 
VentActual.Cor_RecycleRunActive 
L 
10183 
Actual/Set
point 
Start signal Heat Pump 
VentActual.Cor_SumAlarm 
L 
10184 
Alarm 
Status 
Sum alarm: Set if any A or B alarm 
VentActual.Cor_SumAlarmA 
L 
10185 
Alarm 
Status 
A-alarm: Set if any A-alarm in 
controller 
VentActual.Cor_SumAlarmB 
L 
10186 
Alarm 
Status 
B-alarm: Set if any B- or C-alarm in 
controller 
VentActual.Cor_AlaPt(101) 
L 
10187 
Alarm 
Points 
Extra alarm 1 
VentActual.Cor_AlaPt(102) 
L 
10188 
Alarm 
Points 
Extra alarm 2 
VentActual.Cor_AlaPt(103) 
L 
10189 
Alarm 
Points 
Extra alarm 3 
VentActual.Cor_AlaPt(104) 
L 
10190 
Alarm 
Points 
Extra alarm 4 
VentActual.Cor_AlaPt(105) 
L 
10191 
Alarm 
Points 
Extra alarm 5 
VentActual.Cor_AlaPt(106) 
L 
10192 
Alarm 
Points 
Extra alarm 6 
VentActual.Cor_AlaPt(107) 
L 
10193 
Alarm 
Points 
Extra alarm 7 
VentActual.Cor_AlaPt(108) 
L 
10194 
Alarm 
Points 
Extra alarm 8 
VentActual.Cor_AlaPt(109) 
L 
10195 
Alarm 
Points 
Extra alarm 9 
VentActual.Cor_AlaPt(110) 
L 
10196 
Alarm 
Points 
Extra alarm 10 
VentActual.Cor_AlaPt(111) 
L 
10197 
Alarm 
Points 
Extra unit in manual mode 
VentActual.Cor_AlaPt(112) 
L 
10198 
Alarm 
Points 
Malfunction motor control 1 
VentActual.Cor_AlaPt(113) 
L 
10199 
Alarm 
Points 
Malfunction motor control 2 
VentActual.Cor_AlaPt(114) 
L 
10200 
Alarm 
Points 
Motor control 1 external operation 
VentActual.Cor_AlaPt(115) 
L 
10201 
Alarm 
Points 
Motor control 2 external operation 
VentActual.Cor_AlaPt(116) 
L 
10202 
Not used 
Not used 
VentActual.Cor_AlaPt(117) 
L 
10203 
Alarm 
Points 
Motor control 1 in manual mode 