CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
54    Chapter 5 Holding Register 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_Extern
alControl 
X 
40451 
2 
Manual/Auto 
External control: 
Modbus: 
0=Extended run full speed 
1=External stop 
2=No external control 
3=External stop with support control 
BACnet: 
1=Extended run full speed 
2=External stop 
3=No external control 
4=External stop with support control 
VentSettings.Cor_PreHea
tStart 
R 
40452 
8 
Settings, 
PreTreatment 
If outdoor temp. is lower, preheat is 
activated 
VentSettings.Cor_PreCoo
lStart 
R 
40453 
19 
Settings, 
PreTreatment 
If outdoor temp. is higher, precool is 
activated 
VentSettings.Cor_PreTre
atHyst 
R 
40454 
1 
Settings, 
PreTreatment 
Hysteresis to start/stop pretreatment 
VentSettings.Cor_PreTre
atMinDiff 
R 
40455 
1 
Settings, 
PreTreatment 
Min. diff. intake air temp. and outdoor 
air temp. 
VentSettings.Cor_PreTre
atmentAutoMode 
X 
40456 
2 
Settings, 
PreTreatment 
Run mode pretreatment: 
0=Closed 
1=Open 
2=Auto 
VentSettings.Cor_PreTre
atFreeCool 
X 
40457 
0 
Settings, 
PreTreatment 
Select whether pretreatment should be 
activated during free cooling 
VentSettings.Cor_PreTre
atBlockTime 
X 
40458 
6 
Settings, 
PreTreatment 
Hour that pretreatment is blocked if 
diff. intake/outdoor is too low 
VentSettings.Cor_PreTre
atMinRunTime 
X 
40459 
5 
Settings, 
PreTreatment 
Min. runtime (minutes) for 
pretreatment 
VentSettings.Cor_Restart
PowerOn 
X 
40460 
1 
Settings, General 
Automatic restart after power-up (=1) 
VentSettings.Cor_DXFull
Speed 
X 
40461 
0 
Settings, General 
Switch to full speed if DX-Cooling 
VentSettings.Cor_Recycl
eSetPOffset 
R 
40462 
0 
Recirculation 
Offset for recirculation setpoint 
VentSettings.Cor_Recycl
eSetPControl 
X 
40463 
0 
Recirculation 
Select if constant setpoint or setpoint 
adjustment when recirculation runs:  
0=Constant setpoint 
1=Supply air setpoint with adjustment 
VentSettings.Cor_Recycl
eTempControl 
X 
40464 
0 
Recirculation 
Enable supply air temp control when 
recirculation runs: 
0=No temp control 
1=Heating/cooling 
2=Only heating 
3=Only cooling 
VentSettings.Cor_Deman
dCO2Value1 
R 
40465 
800 
CO
2
Activation of demand-controlled 
ventilation, 1/2-speed 