CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 5 Holding Register  49 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_CoolC
oilManual 
R 
40382 
0 
Manual/Auto 
Cooling controller output if manual 
mode 
VentSettings.Cor_Humidi
tyPID_Select 
X 
40383 
2 
Manual/Auto 
Running mode 
Humidification/Dehumidification: 
0=Off 
1=Manual 
2=Auto 
VentSettings.Cor_Humidi
tyPID_ManSet 
R 
40384 
0 
Manual/Auto 
Humidification/Dehumidification 
controller output if manual mode 
VentSettings.Cor_HeatPu
mpAutoMode(0) 
X 
40385 
2 
Manual/Auto 
Running mode P1-Heating: 
0=Manual off 
1=Manual on 
2=Auto 
VentSettings.Cor_ExchP
umpAutoMode 
X 
40386 
2 
Manual/Auto 
Running mode P1-Exchanger: 
0=Manual off 
1=Manual on 
2=Auto 
VentSettings.Cor_CoolPu
mpAutoMode 
X 
40387 
2 
Manual/Auto 
Running mode P1-Cooling: 
0=Manual off 
1=Manual on 
2=Auto 
VentSettings.Cor_FireDa
mperAutoMode 
X 
40388 
2 
Manual/Auto 
Running mode fire damper: 
0=Close 
1=Open 
2=Auto 
VentSettings.Cor_FreshAir
DamperAutoMode 
X 
40389 
2 
Manual/Auto 
Running mode fresh air damper: 
0=Close 
1=Open 
2=Auto 
VentSettings.Cor_Recycle
AirDamperAutoMode 
X 
40390 
2 
Manual/Auto 
Running mode recirculation damper: 
0=Close 
1=Open 
2=Auto 
VentSettings.Cor_ExtractA
irDamperAutoMode 
X 
40391 
2 
Manual/Auto 
Running mode extract air damper: 
0=Close 
1=Open 
2=Auto 
VentActual.Cor_Outdoor 
temp(0) 
R 
40392 
Actual/Setpoint 
Outdoor temperature (Can be modified 
if it’s not connected to a physical 
analogue input). 