CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 5 Holding Register  45 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
TimeHp.Posts(23).From
Date 
R 
40310 
01.01 
Holidays 
Start date holiday period 24 (MM.DD) 
TimeHp.Posts(23).ToDat
e 
R 
40311 
01.01 
Holidays 
End date holiday period 24 (MM.DD) 
VentSettings.Cor_Supply
PID_PGain 
R 
40312 
33°C 
Settings, Control 
Temp 
P-band supply air control 
VentSettings.Cor_Supply
PID_ITime 
R 
40313 
100 s 
Settings, Control 
Temp 
I-time supply air control 
VentSettings.Cor_Exhaus
tPID_PGain 
R 
40314 
100°C 
Settings, Control 
Temp 
P-band extract air control 
VentSettings.Cor_Exhaus
tPID_ITime 
R 
40315 
300 s 
Settings, Control 
Temp 
I-time extract air control 
VentSettings.Cor_RoomP
ID_PGain 
R 
40316 
100°C 
Settings, Control 
Temp 
P-band room air control 
VentSettings.Cor_RoomP
ID_ITime 
R 
40317 
300 s 
Settings, Control 
Temp 
I-time room air control 
VentSettings.Cor_FrostPI
D_PGain 
R 
40318 
100°C 
Settings, Control 
Temp 
P-band switchdown mode 
VentSettings.Cor_FrostPI
D_ITime 
R 
40319 
100 s 
Settings, Control 
Temp 
I-time switchdown mode 
VentSettings.Cor_DeIceP
ID_PGain 
R 
40320 
100°C 
Settings, Control 
Temp 
P-band de-icing 
VentSettings.Cor_DeIceP
ID_ITime 
R 
40321 
100 s 
Settings, Control 
Temp 
I-time de-icing 
VentSettings.Cor_SAFPI
D_PGain 
R 
40322 
500 Pa 
Settings, Control 
Pressure 
P-band pressure control SAF 
VentSettings.Cor_SAFPI
D_ITime 
R 
40323 
60 s 
Settings, Control 
Pressure 
I-time pressure control SAF 
VentSettings.Cor_EAFPI
D_PGain 
R 
40324 
500 Pa 
Settings, Control 
Pressure 
P-band pressure control EAF 
VentSettings.Cor_EAFPI
D_ITime 
R 
40325 
60 s 
Settings, Control 
Pressure 
I-time pressure control EAF 
VentSettings.Cor_SAFAi
rFlowPID_PGain 
R 
40326 
1000 
m
3
/h 
Settings, Control 
Flow 
P-band flow control SAF 
VentSettings.Cor_SAFPI
D_ITime 
R 
40327 
60 s 
Settings, Control 
Flow 
I-time flow control SAF 
VentSettings.Cor_EAFAi
rFlowPID_PGain 
R 
40328 
1000 
m
3
/h 
Settings, Control 
Flow 
P-band flow control EAF 
VentSettings.Cor_EAFPI
D_ITime 
R 
40329 
60 s 
Settings, Control 
Flow 
I-time flow control EAF 
VentSettings.Cor_Humidi
tyPID_PGain 
R 
40330 
100 % 
RH 
Settings, Control 
Humidity 
P-band humidity control 