CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 5 Holding Register  35 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_RoomS
etP 
R 
40019 
21°C 
Supply, Extract and 
Room temperatures 
Room setpoint if room temp control 
function 
VentSettings.Cor_NeedH
eatStart 
R 
40020 
15°C 
Supply, Extract and 
Room temperatures 
Room temp for start the unit if 
intermittent heating control is active 
VentSettings.Cor_NeedH
eatStop 
R 
40021 
21°C 
Supply, Extract and 
Room temperatures 
Room temp for stop the unit if 
intermittent heating control is active 
VentSettings.Cor_NeedC
oolStart 
R 
40022 
30°C 
Supply, Extract and 
Room temperatures 
Room temp for start the unit if 
intermittent cooling control is active 
VentSettings.Cor_NeedC
oolStop 
R 
40023 
28°C 
Supply, Extract and 
Room temperatures 
Room temp for stop the unit if 
intermittent cooling control is active 
VentSettings.Cor_SAFFu
llspeedPressure 
R 
40024 
500 Pa 
SAF/EAF Pressure 
and Flow 
Setpoint full speed supply air fan 
pressure 
VentSettings.Cor_SAFHa
lfspeedPressure 
R 
40025 
250 Pa 
SAF/EAF Pressure 
and Flow 
Setpoint reduced speed supply air fan 
pressure 
VentSettings.Cor_EAFFu
llspeedPressure 
R 
40026 
500 Pa 
SAF/EAF Pressure 
and Flow 
Setpoint full speed extract air fan 
pressure 
VentSettings.Cor_EAFHa
lfspeedPressure 
R 
40027 
250 Pa 
SAF/EAF Pressure 
and Flow 
Setpoint reduced speed extract air fan 
pressure 
VentSettings.Cor_SAFFu
llspeedAirFlow 
R 
40028 
2000 
m
3
/h 
SAF/EAF Pressure 
and Flow 
Setpoint full speed supply air fan flow. 
Scale factor = 1 
VentSettings.Cor_SAFHa
lfspeedAirFlow 
R 
40029 
1000 
m
3
/h 
SAF/EAF Pressure 
and Flow 
Setpoint reduced speed supply air fan 
flow. Scale factor = 1 
VentSettings.Cor_EAFFu
llspeedAirFlow 
R 
40030 
2000 
m
3
/h 
SAF/EAF Pressure 
and Flow 
Setpoint full speed extract air fan flow. 
Scale factor = 1 
VentSettings.Cor_EAFHa
lfspeedAirFlow 
R 
40031 
1000 
m3/h 
SAF/EAF Pressure 
and Flow 
Setpoint reduced speed extract air fan 
flow. Scale factor = 1 
VentSettings.Cor_CO2Se
tpoint 
R 
40032 
1000 
ppm 
CO
2
Setpoint CO
2
VentSettings.Cor_FrostPr
otSPStop 
R 
40033 
25°C 
Frost protection 
Setpoint frost protection if the 
ventilation unit is stopped 
VentSettings.Cor_FrostPr
otPGain 
R 
40034 
5°C 
Frost protection 
P-Gain frost protection when running 
(alarm limit+PGain) 
VentSettings.Cor_DeIcin
gSetpoint 
R 
40035 
-3°C 
Extract air temp/De-
icing exchanger 
Setpoint de-icing temp 
VentSettings.Cor_DeIcin
gHyst 
R 
40036 
1°C 
Extract air temp/De-
icing exchanger 
Hysteresis for stop of de-icing 
VentSettings.Cor_Humidi
tySetpoint 
R 
40037 
50 % RH 
Humidity 
Setpoint humidity room 
VentSettings.Cor_Humidi
tyMaxDuct 
R 
40038 
80 % RH 
Humidity 
Max limit humidity duct 
VentSettings.Cor_Humidi
tyHyst 
R 
40039 
20 % RH 
Humidity 
Hysteresis to start humidity control 
after stop max limitation 