CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
34    Chapter 5 Holding Register 
Chapter 5 Holding Register 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_Supply
Setpoint 
R 
40001 
18°C 
Supply, Extract and 
Room temperatures 
Setpoint supply air temperature when 
constant supply air temperature 
function 
VentSettings.Cor_Curve1
_X1 
R 
40002 
-20°C 
Supply, Extract and 
Room temperatures 
Outdoor temp for first curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_X2 
R 
40003 
-15°C 
Supply, Extract and 
Room temperatures 
Outdoor temp for second curve point 
for outdoor compensated setpoint 
VentSettings.Cor_Curve1
_X3 
R 
40004 
-10°C 
Supply, Extract and 
Room temperatures 
Outdoor temp for third curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_X4 
R 
40005 
-5°C 
Supply, Extract and 
Room temperatures 
Outdoor temp for fourth curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_X5 
R 
40006 
0°C 
Supply, Extract and 
Room temperatures 
Outdoor temp for fifth curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_X6 
R 
40007 
5°C 
Supply, Extract and 
Room temperatures 
Outdoor temp for sixth curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_X7 
R 
40008 
10°C 
Supply, Extract and 
Room temperatures 
Outdoor temp for seventh curve point 
for outdoor compensated setpoint 
VentSettings.Cor_Curve1
_X8 
R 
40009 
15°C 
Supply, Extract and 
Room temperatures 
Outdoor temp for eighth curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_Y1 
R 
40010 
25°C 
Supply, Extract and 
Room temperatures 
Setpoint for first curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_Y2 
R 
40011 
24°C 
Supply, Extract and 
Room temperatures 
Setpoint for second curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_Y3 
R 
40012 
23°C 
Supply, Extract and 
Room temperatures 
Setpoint for third curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_Y4 
R 
40013 
23°C 
Supply, Extract and 
Room temperatures 
Setpoint for fourth curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_Y5 
R 
40014 
22°C 
Supply, Extract and 
Room temperatures 
Setpoint for fifth curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_Y6 
R 
40015 
20°C 
Supply, Extract and 
Room temperatures 
Setpoint for sixth curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_Y7 
R 
40016 
18°C 
Supply, Extract and 
Room temperatures 
Setpoint for seventh curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Curve1
_Y8 
R 
40017 
18°C 
Supply, Extract and 
Room temperatures 
Setpoint for eight curve point for 
outdoor compensated setpoint 
VentSettings.Cor_Exhaus
tSetpoint 
R 
40018 
21°C 
Supply, Extract and 
Room temperatures 
Setpoint extract air temp if extract air 
temp control function 