Chapter 4  Input Register  29 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_ExpDo(3) 
X 
30261 
Digital outputs 
Connected signal on DO4 Exp. Unit 
1: 
(See signal list for DO1) 
VentSettings.Cor_ExpDo(4) 
X 
30262 
Digital outputs 
Connected signal on DO5 Exp. Unit 
1: 
(See signal list for DO1) 
VentSettings.Cor_ExpDo(5) 
X 
30263 
Digital outputs 
Connected signal on DO6 Exp. Unit 
1: 
(See signal list for DO1) 
VentSettings.Cor_ExpDo(6) 
X 
30264 
Digital outputs 
Connected signal on DO7 Exp. Unit 
1: 
(See signal list for DO1) 
VentSettings.Cor_ExpDo(7) 
X 
30265 
Digital outputs 
Connected signal on DO1 Exp. Unit 
2: 
(See signal list for DO1) 
VentSettings.Cor_ExpDo(8) 
X 
30266 
Digital outputs 
Connected signal on DO2 Exp. Unit 
2: 
(See signal list for DO1) 
VentSettings.Cor_ExpDo(9) 
X 
30267 
Digital outputs 
Connected signal on DO3 Exp. Unit 
2: 
(See signal list for DO1) 
VentSettings.Cor_ExpDo(10) 
X 
30268 
Digital outputs 
Connected signal on DO4 Exp. Unit 
2: 
(See signal list for DO1) 
VentSettings.Cor_ExpDo(11) 
X 
30269 
Digital outputs 
Connected signal on DO5 Exp. Unit 
2: 
(See signal list for DO1) 
VentSettings.Cor_ExpDo(12) 
X 
30270 
Digital outputs 
Connected signal on DO6 Exp. Unit 
2: 
(See signal list for DO1) 
VentSettings.Cor_ExpDo(13) 
X 
30271 
Digital outputs 
Connected signal on DO7 Exp. Unit 
2: 
(See signal list for DO1) 
VentActual.Cor_SAFMotorSpeedHz 
R 
30272 
SAF/EAF 
Pressure and 
Flow 
SAF Motor speed Hz 
VentActual.Cor_SAFMotorCurrent 
R 
30273 
SAF/EAF 
Pressure and 
Flow 
SAF Motor current A 
VentActual.Cor_SAFMotorPower 
R 
30274 
SAF/EAF 
Pressure and 
Flow 
SAF Motor Power % of nominal 
VentActual.Cor_SAFAccumPower 
R 
30275 
SAF/EAF 
Pressure and 
Flow 
SAF Accumulated Power 
consumption 