CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
24    Chapter 4 Input Register 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_ExpAi(0) 
X 
30198 
Analogue inputs 
Connected signal on AI1 Exp. Unit 1: 
0=Not used 
1=Outdoor temp 
2=Supplytemp 
3=Extracttemp 
4=Roomtemp1 
5=Roomtemp2 
6=Exhausttemp 
7=Extrasensor 
8=SAF pressure 
9=EAF pressure 
10=Deicingtemp 
11=Frost prot.temp 
12=CO
2
13=Humidity room 
14=Humidity duct 
15=Extra unit temp 
16=External SAF control 
17=External EAF control 
18=SAF pressure 2 
19=Humidity outdoor 
VentSettings.Cor_ExpAi(1) 
X 
30199 
Analogue inputs 
Connected signal on AI2 Exp. Unit 1 
VentSettings.Cor_ExpAi(2) 
X 
30200 
Analogue inputs 
Connected signal on AI3 Exp. Unit 1 
VentSettings.Cor_ExpAi(3) 
X 
30201 
Analogue inputs 
Connected signal on AI4 Exp. Unit 1 
VentSettings.Cor_ExpAi(4) 
X 
30202 
Analogue inputs 
Connected signal on UAI1 Exp. Unit 
1 
VentSettings.Cor_ExpAi(5) 
X 
30203 
Analogue inputs 
Connected signal on UAI2 Exp. Unit 
1 
VentSettings.Cor_ExpAi(6) 
X 
30204 
Analogue inputs 
Connected signal on UAI3 Exp. Unit 
1 
VentSettings.Cor_ExpAi(7) 
X 
30205 
Analogue inputs 
Connected signal on UAI4 Exp. Unit 
1 
VentSettings.Cor_ExpAi(8) 
X 
30206 
Analogue inputs 
Connected signal on AI1 Exp. Unit 2 
VentSettings.Cor_ExpAi(9) 
X 
30207 
Analogue inputs 
Connected signal on AI2 Exp. Unit 2 
VentSettings.Cor_ExpAi(10) 
X 
30208 
Analogue inputs 
Connected signal on AI3 Exp. Unit 2 
VentSettings.Cor_ExpAi(11) 
X 
30209 
Analogue inputs 
Connected signal on AI4 Exp. Unit 2 
VentSettings.Cor_ExpAi(12) 
X 
30210 
Analogue inputs 
Connected signal on UAI1 Exp. Unit 
2 
VentSettings.Cor_ExpAi(13) 
X 
30211 
Analogue inputs 
Connected signal on UAI2 Exp. Unit 
2 
VentSettings.Cor_ExpAi(14) 
X 
30212 
Analogue inputs 
Connected signal on UAI3 Exp. Unit 
2 
VentSettings.Cor_ExpAi(15) 
X 
30213 
Analogue inputs 
Connected signal on UAI4 Exp. Unit 
2 