CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 4  Input Register  17 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_UDi1 
X 
30050 
Universal inputs 
Connected signal on UDI1: 
0=Not used 
1=SAF-Ind 
2=EAF-Ind 
3=P1-Heating 
4=P1-Exchanger 
5=P1-Cooling 
6=Filter guard 
7=Fire alarm 
8=Fire damper-ind 
9=Ext run 1/1 
10=Ext run ½ 
11=External alarm 
12=External switch 
13=Flow guard 
14=Rot.sent.exch 
15=De-icing 
16=Frostprotection 
17=Overheatprotection 
18=Recirculation run 
19=Change over 
20=Filter guard 2 
VentSettings.Cor_UDi2 
X 
30051 
Universal inputs 
Connected signal on UDI2: (See 
signal list for UDI1) 
VentSettings.Cor_UDi3 
X 
30052 
Universal inputs 
Connected signal on UDI3: (See 
signal list for UDI1) 
VentSettings.Cor_UDi4 
X 
30053 
Universal inputs 
Connected signal on UDI4: (See 
signal list for UDI1) 
QAnaOut.AQ1 
R 
30054 
Analogue 
outputs 
Value of AO1 
QAnaOut.AQ2 
R 
30055 
Analogue 
outputs 
Value of AO2 
QAnaOut.AQ3 
R 
30056 
Analogue 
outputs 
Value of AO3 
QAnaOut.AQ4 
R 
30057 
Analogue 
outputs 
Value of AO4 
QAnaOut.AQ5 
R 
30058 
Analogue 
outputs 
Value of AO5 
VentSettings.Cor_Ao1(0) 
X 
30059 
Analogue 
outputs 
Connected signal on AO1: 
0=Not used 
1=Y1-Heating 
2=Y2-Exchanger 
3=Y3-Cooling 
4=SAF 
5=EAF 
6=Y6-Humidity 
7=Split of Y1, Y2 or Y3 
8=Extra unit 
9=Heat/Cool (change over) 
10=Extra sequence Y4 