CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
 - About Corrigo
 - Display, buttons and LEDs
 - The menu system
- Navigating the menus
 - Running mode
 - Temperature
- Setpoint Supply air temperature control
 - Setpoint Outdoor temperature compensated Supply air control
 - Setpoint Cascaded room temperature control
 - Setpoint Cascaded extract air temperature control
 - Setpoint Outdoor compensated room temperature/extract air control
 - Support control heating/Support control cooling
 - Frost protection temperature
 - Exchanger de-icing
 - Heat exchanger efficiency monitoring
 - Recirculation
 - Extra controller unit
 - Enthalpy control
 
 - Air control
- Pressure control SAF (there are also corresponding menus for EAF)
 - Flow control SAF (there are also corresponding menus for EAF)
 - Manual frequency control SAF (there are also corresponding menus for EAF)
 - Frequency control external
 - Frequency control SAF with EAF slave/flow control (also available for opposite function)
 - CO2
 
 - Humidity control
 - Time settings
 - Access rights
 
 - Other functions
 - Index
 
Corrigo ventilation user guide, revision F  The menu system    
9 
Shows the accumulated running times for the fans. 
Selected functions 
In these menus, you can see how some of the most 
important functions have been configured. Changes 
cannot be made. 
Heater, exchanger and cooling type.  
If one of the functions is not used, it will be shown as 
”Not used”. 
This function is used during the summer to cool the 
building night-time using cool outdoor air, thereby 
reducing the need for cooling during the day and saving 
energy. 
Support control is used for adjusting the room 
temperature outside of the normal running time. If there 
is a heating or cooling demand in the room, the unit will 
start and the temperature will be adjusted. 
The fire function determines the settings for the fire 
dampers and the unit’s running mode when a fire alarm 
is activated. 
Frost protection is normally always used in water 
heating systems. The cooling recovery function starts the 
heat exchanger in order to return cooling from the 
extract air when the extract air is colder than the outdoor 
air and cooling is required. 
An analogue input can be configured for an external 
setpoint device e.g. TG-R4/PT1000. 
Running time 
SAF: 14.6 h 
EAF: 14.4 h 
Control function 
Supply air control 
Fan control 
Pressure 
Heating: Water 
Exchanger: Plate exc 
Cooling: Water 
Free cool active: No 
Support control 
active: Yes 
CO2/VOC active 
If timer on 
Fire damper function 
Not active 
Operation when alarm 
Stopped 
Frost protection 
Active 
Cooling recovery 
Not active 
External setpoint 
Not active 










