CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
 - About Corrigo
 - Display, buttons and LEDs
 - The menu system
- Navigating the menus
 - Running mode
 - Temperature
- Setpoint Supply air temperature control
 - Setpoint Outdoor temperature compensated Supply air control
 - Setpoint Cascaded room temperature control
 - Setpoint Cascaded extract air temperature control
 - Setpoint Outdoor compensated room temperature/extract air control
 - Support control heating/Support control cooling
 - Frost protection temperature
 - Exchanger de-icing
 - Heat exchanger efficiency monitoring
 - Recirculation
 - Extra controller unit
 - Enthalpy control
 
 - Air control
- Pressure control SAF (there are also corresponding menus for EAF)
 - Flow control SAF (there are also corresponding menus for EAF)
 - Manual frequency control SAF (there are also corresponding menus for EAF)
 - Frequency control external
 - Frequency control SAF with EAF slave/flow control (also available for opposite function)
 - CO2
 
 - Humidity control
 - Time settings
 - Access rights
 
 - Other functions
 - Index
 
The menu system   Corrigo ventilation user guide, revision F   
16 
Air control 
This menu is only shown if frequency controlled fans have been configured. 
Depending on the choice of fan control, different combinations of the menus below will be 
shown. 
Pressure control SAF (there are also corresponding menus for EAF) 
  Here, Actual and Setpoint values are displayed. This is a 
read-only menu. No settings can be made here. 
Submenu Setpoint values for normal speed (1/1) 
and reduced speed (1/2). 
Submenu outdoor compensation. An outdoor 
temperature dependent compensation of the 
pressure setpoint value can be added. The 
compensation can be set for either the supply air 
fan alone or for both fans. 
Submenu extra compensation. A 
temperature dependent compensation 
similar to the one above but with 
selectable temperature source. 
Flow control SAF (there are also corresponding menus for EAF) 
Setpoint Flow control. Here, Actual and Setpoint values 
are displayed. This is a read-only menu. No settings can 
be made here. 
Submenu Setpoint values for normal speed (1/1) 
and reduced speed (1/2). 
Submenu Outdoor compensation. An outdoor 
temperature dependent compensation of the 
pressure setpoint value can be added. The 
compensation can be set for either the supply air 
fan alone or for both fans. 
Pressure control SAF 
Actual: 480 Pa 
Setp: 490 Pa 
Pressure control SAF 
Setp 1/1: 490 Pa 
Setp 1/2: 300 Pa 
Outdoor comp setp 
 -20 °C = -50 Pa 
 10 °C = 0 Pa 
Act comp: -5 Pa 
Comp sens:Room temp1 
15 °C = 0 Pa 
20 °C = 0 Pa 
25 °C = 0 Pa 
Flow control SAF 
Actual: 1800 m3/h 
Setp: 2000 m3/h 
Flow control SAF 
Setp 1/1: 2000 m3/h 
Setp 1/2: 1000 m3/h 
Outdoor comp setp 
 -15 °C =-200.0 m3/h 
 10 °C = 0.0 m3/h 
Act comp: 0.0 m3/h 