CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
 - About Corrigo
 - Display, buttons and LEDs
 - The menu system
- Navigating the menus
 - Running mode
 - Temperature
- Setpoint Supply air temperature control
 - Setpoint Outdoor temperature compensated Supply air control
 - Setpoint Cascaded room temperature control
 - Setpoint Cascaded extract air temperature control
 - Setpoint Outdoor compensated room temperature/extract air control
 - Support control heating/Support control cooling
 - Frost protection temperature
 - Exchanger de-icing
 - Heat exchanger efficiency monitoring
 - Recirculation
 - Extra controller unit
 - Enthalpy control
 
 - Air control
- Pressure control SAF (there are also corresponding menus for EAF)
 - Flow control SAF (there are also corresponding menus for EAF)
 - Manual frequency control SAF (there are also corresponding menus for EAF)
 - Frequency control external
 - Frequency control SAF with EAF slave/flow control (also available for opposite function)
 - CO2
 
 - Humidity control
 - Time settings
 - Access rights
 
 - Other functions
 - Index
 
The menu system   Corrigo ventilation user guide, revision F   
14 
Exchanger de-icing 
This menu is shown if exchanger de-icing has been 
configured. If the temperature at the de-icing sensor 
drops below the setpoint value, the de-icing function is 
started. It is stopped when the temperature has risen 
above the setpoint plus the set differential. 
Heat exchanger efficiency monitoring 
The function calculates the heat exchanger temperature efficiency in % when the output 
signal to the exchanger is higher than 5 % and the outdoor temperature is lower than 10°C. 
The function requires an extract air sensor, an exhaust air sensor and an outdoor sensor or an 
efficiency sensor, extract air sensor and outdoor sensor. 
When the control signal is lower than 5% or the outdoor temperature is higher than 10°C the 
display will show 0%.  
Recirculation 
The first of the three below menus can be found under Configuration in the controller. The 
fourth menu is located under Temperature. 
Recirculation is a function for mixing the air in the room using the supply air fan. The 
function can be used even when there is no heating or cooling demand. When using 
recirculation control, the extract air fan stops and a recirculation damper opens which allows 
the air to circulate through the unit. 
It is selectable whether or not the extract air fan 
should run during recirculation. 
Deicing exchanger 
 Actual: 11.2°C 
 Setp: -3.0°C 
Hysteresis: 1.0°C 
Efficiency exch 
Actual: 93% 
Output exchanger 
Actual: 100% 
Enable temp  
control when 
recirculation 
Heat and cooling  
Constant or 
setpoint offset 
when recirculation: 
Constant 
EAF running during 
recirculation: No 
Offset SAF when 
frequency control 
and recirculation: 
 0.0 Pa 