CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
 - About Corrigo
 - Display, buttons and LEDs
 - The menu system
- Navigating the menus
 - Running mode
 - Temperature
- Setpoint Supply air temperature control
 - Setpoint Outdoor temperature compensated Supply air control
 - Setpoint Cascaded room temperature control
 - Setpoint Cascaded extract air temperature control
 - Setpoint Outdoor compensated room temperature/extract air control
 - Support control heating/Support control cooling
 - Frost protection temperature
 - Exchanger de-icing
 - Heat exchanger efficiency monitoring
 - Recirculation
 - Extra controller unit
 - Enthalpy control
 
 - Air control
- Pressure control SAF (there are also corresponding menus for EAF)
 - Flow control SAF (there are also corresponding menus for EAF)
 - Manual frequency control SAF (there are also corresponding menus for EAF)
 - Frequency control external
 - Frequency control SAF with EAF slave/flow control (also available for opposite function)
 - CO2
 
 - Humidity control
 - Time settings
 - Access rights
 
 - Other functions
 - Index
 
Corrigo ventilation user guide, revision F  The menu system    
13 
This function operates according to the assumption that 
one may accept a slightly higher indoor temperature 
when it is warm outside and vice versa, providing an 
excellent opportunity for conserving energy. 
Support control heating/Support control cooling 
Support control is normally used when room temperature 
control or extract air control has been configured, to 
prevent a too large offset in temperature when the unit is 
“Off”. 
“Support control Heating” or “Support control Cooling” 
will run if support control is configured, the running 
mode is "Off" (timer control OFF and not in extended 
running) and if conditions call for support control. 
Minimum run time is settable 0 to 720 minutes (FS= 20 minutes).  
Frost protection temperature 
Relevant value for the water temperature at the frost 
protection sensor. Frost protection can be set to function 
either on Y1, Y4 or on both. The function only supports 
a single sensor. 
Outdoor comp setp 
-20.0°C = 25.0°C 
-15.0°C = 24.0°C 
-10.0°C = 23.0°C 
 Outdoor comp setp 
 -5.0°C = 23.0°C 
 0.0°C = 22.0°C 
 5.0°C = 20.0°C 
 Outdoor comp setp 
 10.0°C = 19.0°C 
 20.0°C = 18.0°C 
If cascade control 
max/min supply setp 
Max: 30.0°C 
Min: 12.0°C 
Support heating 
Room temp for 
Start: 15.0°C 
Stop: 21.0°C 
Support cooling 
Room temp for 
Start: 30.0°C 
Stop: 28.0°C 
Frost protection 
 Actual: 30.9°C 










