Free cooling is only activated when the following starting conditions are met
Starting conditions:
•  Less than 4 days have passed since the unit was last in running mode
•  The outdoor temperature during the previous running period exceeded a set limit (71.6°F (22 °C))
•  It is between 00:00 and 07:00:00 in the day (settable)
•  The timer outputs for normal speed, Extended running normal and External stop are Off
•  The timer channel will be On sometime during the recently started 24 hours.
The unit checks the night temperature (indoor and outdoor temperature) during 3 minutes at the set starting 
hour when the fans are started so that the sensors can perform a temperature measurement. If above 
conditions are met the free cooling function is started, if not the unit goes back to OFF position.
If the outdoor sensor is not located in the outdoor air inlet duct and a room sensor has been selected, the 
unit will not start free cooling as long as all the temperatures are not within the start and stop temperature 
intervals.
Stop conditions:
•  Outdoor temp above the set max value (64.4°F (18°C)) or below the set min value (condensation risk, 
50°F (10°C))
.
•  The room temp/extract air temp is below the set stop value (64.4°F (18°C))
.
•  One of the timer outputs for normal speed, External stop or External running normal is On
•  The time is later than 07:00:00.
When free cooling is active, the fans run at normal speed or the set value for pressure/ow control and the 
digital output Free cooling is active. The outputs Y1-Heating, Y2-Heat exchanger and
Y3-Cooling are shut down. After free cooling has been activated, the heating output is blocked for 60 
minutes (congurable time).
Note
The following is only valid if the free cooling function is set to Active in the program menu.
4.4 Free Cooling Description
This function is used during the warm period to save energy by using cold outdoor air, e.g. during night 
time, to cool down the building.
→ Log off Log off
No
Actual 
level: None
Log off from system level by 
changing “No” to “Yes” with the 
“OK” and “UP/DOWN” buttons
Automatic logoff after 6 minutes 
of inactivity.
→ Change 
password
Change password 
for
level:None
New password 
xxxx
Set a new password for the level 
of your choice.
Can only be done once logged 
on to the service level.