Communication guide  Commonly used signals  7 
Chapter 3  Commonly used signals 
To simplify system integration, a register of commonly used signals is provided below. Please refer 
to the document Corrigo ventilation variables for EXOline, Modbus and BACnet for a complete list. 
3.1 Input Status 
Signal name 
EXOL type 
Modbus address 
BACnet 
Default value 
Function  Description 
VentActual.Cor_
ExtendedRunActi
veFull 
L  8  BV, 20008    Actual/Setpoint  Set if extended operation 
full speed 
VentActual.Cor_
ExtendedRunActi
veHalf 
L  9  BV, 20009    Actual/Setpoint  Set if extended operation 
half speed 
VentActual.Cor_
AlaPt(1) 
… 
VentActual.Cor_
AlaPt(48) 
L  33 
… 
80 
BV, 20033 
… 
BV, 20080 
  Alarm Points  Run Error Supply Air 
Fan 
0=No alarm 
1=Alarm 
… 
Internal battery error 
VentActual.Cor_
AlaPt(49) 
… 
VentActual.Cor_
AlaPt(100) 
L  90 
… 
141 
BV, 20090 
… 
BV, 20141 
  Alarm Points  Sensor error Supply Air 
temp 
… 
Low temp Extra sensor 5 
3.2 Holding Register – Setpoint settings 
Holding register values are adjustable (read/write). 
Signal name 
EXOL type 
Modbus address 
BACnet 
Default value 
Function  Description 
VentSettings.Cor_
SupplySetpoint 
R  1  AV, 30001  18°C  Supply, 
Extract and 
Room 
temperatures 
Setpoint supply air 
temperature when 
constant supply air 
temperature function 
VentSettings.Cor_
ExhaustSetpoint 
R  18  AV, 30018  21°C  Supply, 
Extract and 
Room 
temperatures 
Setpoint extract air temp 
if extract air temp control 
function 