Communication guide  Appendix Alarm list  15 
No.  Alarm text  Prio  Description 
39  Manual Extract Air Fan mode  C  Extract air fan in manual control 
40  Freq. EAF Manual  C  Signal to SAF frequency converter in manual control 
41  Heating Manual Manual  C  Heating output in manual control 
42 
Manual exchanger control 
C 
Heat exchanger output in manual control 
43 
Manual cooler control 
C 
Cooling output in manual control 
44  Manual P1-Heater  C  Heating circulation pump in manual control 
45  Manual P1-Exchanger  C  Exchanger circulation pump in manual control 
46  Manual P1-Cooler  C  Cooling circulation pump in manual control 
47  Fire damp. Manual  C  Fire dampers in manual control 
48 
Internal battery error 
A 
Internal battery needs replacing 
49 
Sensor error Supply Air temp 
B 
Malfunction of connected sensor 
50 
Sensor error Extract Air temp 
B 
Malfunction of connected sensor 
51  Sensor error Room temp 1  B  Malfunction of connected sensor 
52  Sensor error Room temp 2  B  Malfunction of connected sensor 
53  Sensor error Exhaust air temp  B  Malfunction of connected sensor 
54  Sensor error Extra sensor  B  Malfunction of connected sensor 
55 
Sensor error SAF pressure 
B 
Malfunction of connected sensor 
56 
Sensor error EAF pressure 
B 
Malfunction of connected sensor 
57  Sensor error Deicing temp  B  Malfunction of connected sensor 
58  Sensor error Frost Protection temp  B  Malfunction of connected sensor 
59  Sensor error CO2  B  Malfunction of connected sensor 
60  Sensor error Humidity Room  B  Malfunction of connected sensor 
61  Sensor error Humidity Duct  B  Malfunction of connected sensor  
62 
Sensor error Extra unit temp 
B 
Malfunction of connected sensor 
63 
Sensor error External control SAF 
B 
Malfunction of connected sensor 
64  Sensor error External control EAF  B  Malfunction of connected sensor 
65  Sensor error SAF Pressure 2  B  Malfunction of connected sensor 
66  Sensor error Humidity outdoor  B  Malfunction of connected sensor 
77  Alarm Frequency converter SAF  A  Malfunction of frequency converter SAF 
78 
Alarm Frequency converter EAF 
A 
Malfunction of frequency converter EAF 
79 
Communication error Frequency SAF 
C 
Communication problem with Vacon NXL 
80 
Communication error Frequency EAF 
C 
Communication problem with Vacon NXL 
81  Communication error Expansion unit 1  C  Communication problem with a controller connected to port 2 
82  Communication error Expansion unit 2  C  Communication problem with a controller connected to port 2 
83  Warning Frequency converter SAF  C   
84  Warning Frequency converter EAF  C   
85 
Output in manual mode 
C 
Analogue or digital output in manual mode 
86 
Time for service 
C 
Time for service 
87 
Manual Y4-Extra Sequence control 
C 
Y4-Extra sequence in manual control 
88  Restart blocked after power failure  C  Restart blocked after power failure 
89  Manual Y5-Extra Sequence control  C  Y5-Extra sequence in manual control 
90  Filter guard 2  B  Filter guard pressure switch activated 
91  High temp Extra sensor 1  -  High temperature Extra sensor 1 
92 
Low temp Extra sensor 1 
- 
Low temperature Extra sensor 1 