Corrigo ventilation Communication Guide 3.3 manu
Table Of Contents
Communication guide  Commonly used signals  13 
Signal name 
EXOL type 
Modbus address 
BACnet 
Default value 
Function  Description 
VentActual.Cor_C
O2Sensor 
R  17  AV, 
40017 
  CO2  CO2 (ppm) 
VentActual.Cor_Fr
ostprotectionTemp 
R  19  AV, 
40019 
  Frost protection  Frost protection temp 
VentActual.Cor_De
IcingTemp 
R  21  AV, 
40021 
  Extract air 
temp/De-icing 
exchanger 
De-icing temp 
exchanger 
VentActual.Cor_Hu
midityRoom 
R  23  AV, 
40023 
  Humidity  Humidity room 
VentActual.Cor_Ex
traSensor 
R  25  AV, 
40025 
  Additional sensor/ 
External setpoint 
Extra sensor 1/External 
setpoint (depending on 
configuration) 
VentActual.Cor_He
atCV1(0) 
R  119  AV, 
40119 
  Analogue outputs  Control signal heating 
Y1 (0...10 V) 
VentActual.Cor_Ex
chCV1 
R  120  AV, 
40120 
  Analogue outputs  Control signal 
exchanger Y2 (0...10 
V) 
VentActual.Cor_Co
olCV1 
R  121  AV, 
40121 
  Analogue outputs  Control signal cooler 
Y3 (0...10 V) 
VentActual.Cor_S
AF 
R  122  AV, 
40122 
  SAF/EAF 
Pressure and Flow 
Control signal supply 
air fan (0...10 V) 
VentActual.Cor_E
AF 
R  123  AV, 
40123 
  SAF/EAF 
Pressure and Flow 
Control signal extract 
air fan (0...10 V) 
VentActual.Cor_Un
itRunMode 
X  284  MSV, 
40284 
  Actual/Setpoint  Unit run mode: 
Modbus: 
0=Off  
1=Reduced speed  
2=Normal speed  
3=Stop because of 
alarm 
BACnet: 
1=Off  
2=Reduced speed  
3=Normal speed  
4=Stop because of 
alarm 
VentActual.Cor_Fil
terGuard1AI 
R  301  AV, 
40301 
  Actual/Setpoint  Analogue filter 1 value 
(Pa) 
VentActual.Cor_Fil
terGuard2AI 
R  302  AV, 
40302 
Actual/Setpoint 
Analogue filter 2 value 
(Pa) 