CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
74    Chapter 7 Frequency converters 
Omron  frequency  converters  are  controlled  via  Modbus.  Communication,  alarms  and  certain 
indications can be read. 
The following signals can be read/written from/to the frequency converter: 
Address 
Modbus register 
Name 
Scaling 
Type 
3 
30003, 40003 
FB Speed reference (SP) 
10 
% 
2 
30002, 40002 
Password 
- 
- 
36 
30036, 40036 
Motor frequency 
100 
Hz 
63 
30063, 40063 
Motor speed 
1 
+/- Rpm 
39 
30039, 40039 
Current 
10 
A 
40 
30040, 40040 
Output 
10 
kW 
38 
30038, 40038 
DC voltage 
10 
V 
33 
30033, 40033 
Status change 
- 
Binary 
34 
30034, 40034 
Alarm 
- 
Binary 
93 
30093, 40093 
Acc. Motor output 
1 
kW 
The variables presented in the display of the Corrigo are: 
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh). 
Emerson Commander 
Connections RS485-RJ45: 
  RJ45:2 (orange) is connected to B on port 1 or 2 
  RJ45:7 (white/brown) is connected to A on port 1 or 2 
  Possible termination resistor is connected between RJ45:1 (white/orange) and RJ45:8 (brown). 
If Modbus communication is not initialised after powering up, disconnect the termination resistor and 
try again. 
Terminals 
  Connect terminal B4 (Drive enabled) to B2 (+24V) 
  Connect terminal B5 (Forward) to B2 (+24V) 
Parameters 
The following parameters must be set from the display of the frequency converter: 
  44: Slave address, set to = 1 (default) for Supply air fan and = 2 for Exhaust air fan 
  43: Baud rate: 9.6 (default: 19.2) 
  Default values should be used for remaining parameters. 
Changing parameters 
  Deactivate  the  unit.  The  display  should  read  “iH  0.0”.  This  is  performed  by 
opening terminal B4. 
  Set parameter 10 to ”L3”, i.e. all parameters up to and including 95 can then be altered. 
  Set parameter 43 to 9.6 (9600 baud). 