CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
64    Chapter 6 Input Status Register 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentActual.Cor_AlaPt(47) 
L 
10079 
Alarm 
Points 
Manual fire damper 
VentActual.Cor_AlaPt(48) 
L 
10080 
Alarm 
Points 
Internal battery error 
VentActual.Cor_SAFStart1(0) 
L 
10081 
SAF/EAF 
Pressure 
and Flow 
Start signal full speed supply air fan 
VentActual.Cor_EAFStart1 
L 
10082 
SAF/EAF 
Pressure 
and Flow 
Start signal full speed extract air fan 
VentActual.Cor_SAFStart2 
L 
10083 
SAF/EAF 
Pressure 
and Flow 
Start signal half speed supply air fan 
VentActual.Cor_EAFStart2 
L 
10084 
SAF/EAF 
Pressure 
and Flow 
Start signal half speed extract air fan 
VentActual.Cor_HeatPumpStart(0) 
L 
10085 
Actual/Set
point 
Start signal Heat Pump 
VentActual.Cor_ExchPumpStart 
L 
10086 
Actual/Set
point 
Start signal Exchanger 
VentActual.Cor_CoolPumpStart 
L 
10087 
Actual/Set
point 
Start signal Cool Pump 
VentActual.Cor_SAFFrequencyStart 
L 
10088 
SAF/EAF 
Pressure 
and Flow 
Start signal frequencer supply air fan 
VentActual.Cor_EAFFrequencyStart 
L 
10089 
SAF/EAF 
Pressure 
and Flow 
Start signal frequencer extract air fan 
VentActual.Cor_AlaPt(49) 
L 
10090 
Alarm 
Points 
Sensor error supply air temp. 
VentActual.Cor_AlaPt(50) 
L 
10091 
Alarm 
Points 
Sensor error extract air temp. 
VentActual.Cor_AlaPt(51) 
L 
10092 
Alarm 
Points 
Sensor error room temp. 1 
VentActual.Cor_AlaPt(52) 
L 
10093 
Alarm 
Points 
Sensor error room temp. 2 
VentActual.Cor_AlaPt(53) 
L 
10094 
Alarm 
Points 
Sensor error extract air temp. 
VentActual.Cor_AlaPt(54) 
L 
10095 
Alarm 
Points 
Sensor error extra sensor 
VentActual.Cor_AlaPt(55) 
L 
10096 
Alarm 
Points 
Sensor error SAF pressure 
VentActual.Cor_AlaPt(56) 
L 
10097 
Alarm 
Points 
Sensor error EAF pressure 