30    Chapter 4 Input Register 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentActual.Cor_EAFMotorSpeedHz 
R 
30276 
SAF/EAF 
Pressure and 
Flow 
EAF Motor speed Hz 
VentActual.Cor_EAFMotorCurrent 
R 
30277 
SAF/EAF 
Pressure and 
Flow 
EAF Motor current A 
VentActual.Cor_EAFMotorPower 
R 
30278 
SAF/EAF 
Pressure and 
Flow 
EAF Motor Power % of nominal 
VentActual.Cor_EAFAccumPower 
R 
30279 
SAF/EAF 
Pressure and 
Flow 
EAF Accumulated Power consuption 
VentActual.Cor_ExtraUnitCV1(0) 
R 
30280 
Extra Unit 
Control signal Extra Unit 
(0...10 V) 
VentActual.Cor_ExtraUnitPID1_Outpu
t(0) 
R 
30281 
Extra Unit 
Extra Unit controller output (0...100 
%) 
VentActual.Cor_HeatCoolCV1 
R 
30282 
Analogue 
outputs 
Control signal Heating or Cooling 
controlled by changeover 
(0...10 V) 
VentActual.Cor_ExtraSeqCV1 
R 
30283 
Analogue 
outputs 
Control signal extra sequence Y4 
(0...10 V) 
VentActual.Cor_UnitRunMode 
X 
30284 
Actual/Setpoint 
Unit run mode: 
Modbus: 
0=Off 
1=Reduced speed 
2=Normal speed 
3=Stop because of alarm 
BACnet: 
1=Off 
2=Reduced speed 
3=Normal speed 
4=Stop because of alarm 
AlaData.AlaPt88_Status 
X 
30285 
Alarm Status 
Restart blocked after power-on 
VentActual.Cor_IntakeAirTemp 
R 
30286 
Actual/Setpoint 
Intake air temperature 
VentActual.Cor_ExtraSensor2 
R 
30287 
Actual/Setpoint 
Extrasensor 2 temperature 
VentActual.Cor_ExtraSensor3 
R 
30288 
Actual/Setpoint 
Extrasensor 3 temperature 
VentActual.Cor_ExtraSensor4 
R 
30289 
Actual/Setpoint 
Extrasensor 4 temperature 
VentActual.Cor_ExtraSensor5 
R 
30290 
Actual/Setpoint 
Extrasensor 5 temperature 
VentActual.Cor_ExtraSAFPressure 
R 
30291 
SAF/EAF 
Pressure and 
Flow 
Extrasensor SAF Pressure 
VentActual.Cor_ExtraEAFPressure 
R 
30292 
SAF/EAF 
Pressure and 
Flow 
Extrasensor EAF Pressure 