CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
20    Chapter 4 Input Register 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
AlaData.AlaPt26_Status 
X 
30096 
Alarm Status 
Low efficiency 
AlaData.AlaPt27_Status 
X 
30097 
Alarm Status 
Sensor error outdoor temp 
AlaData.AlaPt28_Status 
X 
30098 
Alarm Status 
Analogue deicing 
AlaData.AlaPt29_Status 
X 
30099 
Alarm Status 
Rotation guard exchanger 
AlaData.AlaPt30_Status 
X 
30100 
Alarm Status 
Fire damper malfunction 
AlaData.AlaPt31_Status 
X 
30101 
Alarm Status 
Supply air fan control error 
AlaData.AlaPt32_Status 
X 
30102 
Alarm Status 
Extract air fan control error 
AlaData.AlaPt33_Status 
X 
30103 
Alarm Status 
Supply air fan external operation 
AlaData.AlaPt34_Status 
X 
30104 
Alarm Status 
Extract air fan external operation 
AlaData.AlaPt35_Status 
X 
30105 
Alarm Status 
Ventilation manual mode 
AlaData.AlaPt36_Status 
X 
30106 
Alarm Status 
Manual supply air control 
AlaData.AlaPt37_Status 
X 
30107 
Alarm Status 
Supply air fan manual mode 
AlaData.AlaPt38_Status 
X 
30108 
Alarm Status 
Manual supply air fan freq. control 
AlaData.AlaPt39_Status 
X 
30109 
Alarm Status 
Extract air fan manual mode 
AlaData.AlaPt40_Status 
X 
30110 
Alarm Status 
Manual extract air fan freq. control 
AlaData.AlaPt41_Status 
X 
30111 
Alarm Status 
Manual heater control 
AlaData.AlaPt42_Status 
X 
30112 
Alarm Status 
Manual exchanger control 
AlaData.AlaPt43_Status 
X 
30113 
Alarm Status 
Manual cooler control 
AlaData.AlaPt44_Status 
X 
30114 
Alarm Status 
Manual P1 heater 
AlaData.AlaPt45_Status 
X 
30115 
Alarm Status 
Manual P1 exchanger 
AlaData.AlaPt46_Status 
X 
30116 
Alarm Status 
Manual P1 cooler 
AlaData.AlaPt47_Status 
X 
30117 
Alarm Status 
Manual fire damper 
AlaData.AlaPt48_Status 
X 
30118 
Alarm Status 
Internal battery error 
VentActual.Cor_HeatCV1(0) 
R 
30119 
Analogue 
outputs 
Control signal heating Y1 (0...10 V) 
VentActual.Cor_ExchCV1 
R 
30120 
Analogue 
outputs 
Control signal exchanger Y2 (0...10 
V) 
VentActual.Cor_CoolCV1 
R 
30121 
Analogue 
outputs 
Control signal cooler Y3 (0...10 V) 
VentActual.Cor_SAF 
R 
30122 
SAF/EAF 
Pressure and 
Flow 
Control signal supply air fan (0...10 
V) 
VentActual.Cor_EAF 
R 
30123 
SAF/EAF 
Pressure and 
Flow 
Control signal extract air fan (0...10 
V) 
VentActual.Cor_Humidity 
R 
30124 
Humidity 
Control signal humidity (0...10 V) 
VentActual.Cor_Split 
R 
30125 
Analogue 
outputs 
Control signal split (0...10 V) 