VentActual.Cor_Outdoor temp(0) 
R 
30001 
Actual/Setpoint 
Outdoor temperature (read-only) 
VentActual.Cor_Efficiency 
R 
30002 
Actual/Setpoint 
Efficiency in % for exchanger 
VentActual.Cor_RunMode 
X 
30003 
Actual/Setpoint 
Modbus: 
0=Stopped 
1=Starting up 
2=Starting reduced speed 
3=Starting full speed 
4=Starting normal run 
5=Normal run 
6=Support control heating 
7=Support control cooling 
8=CO
2
 run 
9=Night cooling 
10=Full speed stop 
11=Stopping fan 
BACnet: 
1=Stopped 
2=Starting up 
3=Starting reduced speed 
4=Starting full speed 
5=Starting normal run 
6=Normal run 
7=Support control heating 
8=Support control cooling 
9=CO
2
 run 
10=Night cooling 
11=Full speed stop 
12=Stopping fan 
VentActual.Cor_SAFRunTime 
R 
30004 
Actual/Setpoint 
Running time (hour) supply air fan 
VentActual.Cor_EAFRunTime 
R 
30005 
Actual/Setpoint 
Running time (hour) extract air fan 
VentActual.Cor_ExtendedRunMin 
I 
30006 
Actual/Setpoint 
Number of minutes extended 
operation 
VentActual.Cor_SupplyAirTemp 
R 
30007 
Supply, Extract 
and Room 
temperatures 
Supply air temperature 
VentActual.Cor_SupplyPID_SetP 
R 
30008 
Supply, Extract 
and Room 
temperatures 
Calculated setpoint supply air 
temperature when outdoor 
compensated control function or 
cascade control is active 
VentActual.Cor_ExhaustAirTemp: 
(NB: This is actually the variable for 
the extract air temp!) 
R 
30009 
Supply, Extract 
and Room 
temperatures 
Extract air temperature 