CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 7 Frequency converters  77 
ECBlue 
ECBlue  frequency  converters  are  controlled  via  Modbus.  Communication,  alarms  and  certain 
indications can be read. 
The following signals can be read/written from/to the frequency converter: 
Address 
Modbus register 
Name 
Scale 
Type 
3 
30003,40003 
FB Speed reference (SP) 
1 
% 
5 
30005,40005 
FB Control word 
- 
0 = Off 
3 = On 
15 
30015,40015 
RPM 
Rpm 
16 
30016,40016 
Current 
100 
A 
34 
30034,40034 
Output 
1 
kW 
21  
30021,40021 
DC voltage 
1  
V 
13  
30013,40013 
Alarm 
- 
Error code 
Eltwin A/S EC controller (for heat exchangers) 
Communication takes place using address 7, 9600 bps, 8 bits, no parity and 1 stop bit. 
Version 1.01, 2015-04-03 
Address 
Modbus register 
Name 
Scaling 
Type 
1 
30001 
Running mode 
- 
Bit 0 = Operation 
0: Stop 
1: Run 
Bit 3 = Reset 
1: Reset 
2 
30002 
Speed 
1 
0…100.0 % 
3 
30003 
Supply voltage 
- 
V(RMS) 
4 
30004 
Error code 
1 
Bit 0: Excess 
current/Ground fault 
Bit 1: Excess current 
from DC link 265V~ 
Bit 2: Undervoltage 
from DC link 170V~ 
Bit 3: Hardware error 
Bit 4: External error, 
input 
Bit 5: Overload 
Bit 6: Overheating, 
stop 
Bit 7: Overheating, 
reduced 
Bit 8: Rotor cover 
error 
Bit 9: Rotor cover 
input 
Bit 10: DIP 1 
Bit 11: DIP 2 
Bit 12: DIP 3 
Bit 13: DIP 4 
Bit 14: Not used 
Bit 15: 
Communication error 
5 
30005 
Speed output 
1 
RPM 
6 
30006 
Voltage output 
1 
Volt 
7 
30007 
Motor current, DC link 
1 
mA 
8 
30008 
Motor output 
1 
W 