CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 7 Frequency converters  73 
Lenze 
No settings necessary. 
Lenze  frequency  converters  are  controlled  via  Modbus.  Communication,  alarms  and  certain 
indications can be read. 
The following signals can be read/written from/to the frequency converter: 
Address 
Modbus register 
Name 
Scaling 
Type 
49 
32049, 42049 
Password 
- 
- 
50 
32050, 42050 
Parameter version 
- 
- 
45 
30045, 40045 
FB Speed reference (SP) 
50 
% 
2 
30002, 40002 
FB Status word 
- 
Binary 
512 
32512, 42512 
Acc. Motor output 
1 
kW 
528 
32528, 42528 
Motor frequency 
10 
Hz 
509 
32509, 42509 
Current 
1 
A 
511 
32511, 42511 
Output 
1000 
kW 
506 
31506, 41506 
DC voltage 
1 
V 
30 
32110, 42110 
Active error 
- 
Error code 
27 
32027, 42027 
FB Status word 
- 
Binary 
The variables presented in the display of the Corrigo are: 
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh). 
Omron V1000 
Connected via RS485: 
  R+ is connected to S+ 
  R- is connected to S- 
  R+/S+ is connected to B on port 1 or 2 
  R-/S- is connected to A on port 1 or 2 
Parameters 
The following parameters must be set from the display of the frequency converter: 
  H5-01 (0x425): Slave address, set to = 1 for Supply air fan and = 2 for Exhaust air fan 
  H5-07 (0x42B): RTS Control, set to = 1 (enabled) for activation of RS485 
  o1-03 (0x502): Frequency reference units, set to = 1 for 0-100%. 
  H5-03 (0x427): Parity, set to = 0 (no parity) 
Default values should be used for remaining parameters. The following values may not be changed: 
  H5-02 (0x426): Communication speed, default =3 (9600) 
  H5-04 (0x428): Stopping method after communication error, default = 3 (no stop) 
  H5-11 (0x43C): Communication Enter Function, default=1 (Enter command not 
necessary) 
  H5-12 (0x43D): Run command, default=0 (bit 0=forward start/stop, bit 1= reverse 
start/stop) 
  b1-01 (0x180): Frequency Reference selection 1, default = 2 (via Modbus) 
  b2-01 (0x181): Run command selection 1, default = 2 (via Modbus) 