CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
72    Chapter 7 Frequency converters 
Chapter 7 Frequency converters 
Version 3.4 of Corrigo ventilation supports the frequency converters listed below: 
  Vacon NXL 
  Lenze 
  Omron V1000 
  Emerson Commander 
  LS 
  EBM 
  Danfoss FC 101 
  ABB ACS 
  EC Blue 
When communicating via frequency converters through Modbus, it is sometimes necessary to change 
certain settings in the frequency converter. 
Two parallel connected frequency converters for supply air and two parallel connected frequency 
converters for extract air can be run. The supply air fan will have address 1 and the parallel supply air 
fan address 3. The extract air fan will have address 2 and the parallel extract air fan address 4. 
Below is described what settings are necessary in the various models: 
Vacon NXL 
No settings necessary. Vacon NXL frequency converters are controlled via Modbus. Communication, 
alarms and certain indications can be read. 
The following signals can be read/written from/to the frequency converter: 
Address 
Modbus register 
Name 
Scaling 
Type 
2003 
32003, 42003 
FB Speed reference (SP) 
1000 
% 
2001 
32001, 42001 
FB Status word 
- 
Binary 
11 
30011, 40011 
Acc. Motor output 
1 
kW 
80 
30080, 40080 
Amount of decimals for Acc. Motor 
output 
1 
kWh 
2103 
32103, 42103 
FB Motor speed 
100 
% 
2105 
32105, 42105 
Motor speed 
1 
+/- Rpm 
2106 
32106, 42106 
Current 
100 
A 
2107 
32107, 42107 
Torque 
10 
+/- % (of nominal) 
1501 
31501, 41501 
Output 
1000 
kW 
2110 
32110, 42110 
DC voltage 
1 
V 
2111 
32111, 42111 
Active error 
- 
Error code 
2101 
32101, 42101 
FB Status word 
- 
Binary 
The variables presented in the display of the Corrigo are: 
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh). 