CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 6 Input Status Register  61 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
QDig.DI3 
L 
10016 
Digital 
inputs 
Value of DI3 
QDig.DI4 
L 
10017 
Digital 
inputs 
Value of DI4 
QDig.DI5 
L 
10018 
Digital 
inputs 
Value of DI5 
QDig.DI6 
L 
10019 
Digital 
inputs 
Value of DI6 
QDig.DI7 
L 
10020 
Digital 
inputs 
Value of DI7 
QDig.DI8 
L 
10021 
Digital 
inputs 
Value of DI8 
QDig.DI9 
L 
10022 
Universal 
inputs 
Value of UDI1 
QDig.DI10 
L 
10023 
Universal 
inputs 
Value of UDI2 
QDig.DI11 
L 
10024 
Universal 
inputs 
Value of UDI3 
QDig.DI12 
L 
10025 
Universal 
inputs 
Value of UDI4 
QDig.Dq1 
L 
10026 
Digital 
outputs 
Value of DO1 
QDig.Dq2 
L 
10027 
Digital 
outputs 
Value of DO2 
QDig.Dq3 
L 
10028 
Digital 
outputs 
Value of DO3 
QDig.Dq4 
L 
10029 
Digital 
outputs 
Value of DO4 
QDig.Dq5 
L 
10030 
Digital 
outputs 
Value of DO5 
QDig.Dq6 
L 
10031 
Digital 
outputs 
Value of DO6 
QDig.Dq7 
L 
10032 
Digital 
outputs 
Value of DO7 
VentActual.Cor_AlaPt(1) 
L 
10033 
Alarm 
Points 
Supply air fan malfunction 
0=No alarm 
1=Alarm 
VentActual.Cor_AlaPt(2) 
L 
10034 
Alarm 
Points 
Extract air fan malfunction 
VentActual.Cor_AlaPt(3) 
L 
10035 
Alarm 
Points 
P1 heater malfunction 
VentActual.Cor_AlaPt(4) 
L 
10036 
Alarm 
Points 
P1 cooler malfunction 