60    Chapter 6 Input Status Register 
Chapter 6 Input Status Register 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
TimePro.TimeGroupFanFullSpeed 
L 
10001 
Actual/Set
point 
Set if timechannel full speed is active 
TimePro.TimeGroupFanHalfSpeed 
L 
10002 
Actual/Set
point 
Set if timechannel reduced speed is 
active 
TimePro.TimeGroupCor_ExtraTimeG
roup1 
L 
10003 
Actual/Set
point 
Set if timer output 1 is active 
TimePro.TimeGroupCor_ExtraTimeG
roup2 
L 
10004 
Actual/Set
point 
Set if timer output 2 is active 
TimePro.TimeGroupCor_ExtraTimeG
roup3 
L 
10005 
Actual/Set
point 
Set if timer output 3 is active 
TimePro.TimeGroupCor_ExtraTimeG
roup4 
L 
10006 
Actual/Set
point 
Set if timer output 4 is active 
TimePro.TimeGroupCor_ExtraTimeG
roup5 
L 
10007 
Actual/Set
point 
Set if timer output 5 is active 
VentActual.Cor_ExtendedRunActive
Full 
L 
10008 
Actual/Set
point 
Set if extended operation full speed 
VentActual.Cor_ExtendedRunActive
Half 
L 
10009 
Actual/Set
point 
Set if extended operation half speed 
VentActual.Cor_NeedHeatActive 
L 
10010 
Supply, 
Extract and 
Room 
temperatur
es 
Set if ongoing support heating 
VentActual. Cor_NeedCoolActive 
L 
10011 
Supply, 
Extract and 
Room 
temperatur
es 
Set if ongoing support cooling 
VentActual.Cor_DemandCO2Active 
L 
10012 
CO
2
Set if ongoing support CO
2
VentActual.Cor_DeIcingActive 
L 
10013 
Extract air 
temp/De-
icing 
exchanger 
Set if ongoing de-icing 
QDig.DI1 
L 
10014 
Digital 
inputs 
Value of DI1 
QDig.DI2 
L 
10015 
Digital 
inputs 
Value of DI2 