CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 5 Holding Register  59 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_FireEA
FSpeed 
R 
40526 
-1 
Settings, Fire mode 
SAF speed in fire mode 0…100 %, -1 = 
fan runs in normal speed conditions 
VentSettings.Cor_Cmp1P
ressure 
R 
40527 
0 
Settings, Control 
Pressure 
Pressure compensation at low point. 
Extra comp. curve pressure/flow 
setpoint. 
VentSettings.Cor_Cmp1
Value 
R 
40528 
15 
Settings, Control 
Pressure 
Temperature for low point. Extra comp. 
curve pressure/flow setpoint. 
VentSettings.Cor_Cmp2P
ressure 
R 
40529 
0 
Settings, Control 
Pressure 
Pressure compensation at middle point. 
Extra comp. curve pressure/flow 
setpoint. 
VentSettings.Cor_Cmp2
Value 
R 
40530 
20 
Settings, Control 
Pressure 
Temperature for middle point. Extra 
comp. curve pressure/flow setpoint. 
VentSettings.Cor_Cmp3P
ressure 
R 
40531 
0 
Settings, Control 
Pressure 
Pressure compensation at high point. 
Extra comp. curve pressure/flow 
setpoint. 
VentSettings.Cor_Cmp3
Value 
R 
40532 
25 
Settings, Control 
Pressure 
Temperature for high point. Extra 
comp. curve pressure/flow setpoint. 