CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 5 Holding Register  55 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_Deman
dCO2Value2 
R 
40466 
1000 
CO
2
Activation of demand-controlled 
ventilation, 1/1-speed 
VentSettings.Cor_Deman
dCO2Diff 
R 
40467 
160 
CO
2
Hysteresis for stop of demand 
controlled ventilation (ppm) 
VentSettings.Cor_Cascad
eTemp 
R 
40468 
13 
Supply, Extract and 
Room temperatures 
Outdoor temp for switching between 
outdoor compensated or cascade 
control if Cor_VentControl = 4 or 5 (if 
higher outdoor temp then cascade 
control) 
VentSettings.Cor_ExtraS
eqY5AutoMode 
X 
40469 
2 
Manual/Auto 
Run mode Extra seq coil Y5 (0=Off, 
1=Manual, 2=Auto) 
VentSettings.Cor_ExtraS
eqY5Manual 
R 
40470 
0 
Manual/Auto 
Manual setting Extra seq coil Y5 
if manual mode 
VentSettings.Cor_ExtraS
eqY5Min 
R 
40471 
0 
Actual/Setpoint 
Min. limit for Y5 in Auto mode 
VentSettings.Cor_Reduce
dSetPOffset 
R 
40472 
0 
Actual/Setpoint 
Temperature setpoint offset in reduced 
speed 
VentSettings.Cor_Change
OverSelect 
X 
40473 
2 
Settings, General 
Select change-over external: 
Modbus: 
0=Heating 
1=Cooling 
2=Auto 
BACnet: 
1=Heating 
2=Cooling 
3=Auto 
VentSettings.Cor_VentC
ontrol 
X 
40474 
0 
Settings, General 
Select temperature control mode: 
0=Const. supply air 
1=Outdoor compensated supply air 
2=Cascade room temp control 
3=Extract temp control 
4=Outdoor dependent supply or room 
temp 
5=Outdoor dependent supply or extract 
temp 
6=Cascade outdoor compensated room 
temp control 
7=Cascade outdoor compensated 
extract temp control 