CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
52    Chapter 5 Holding Register 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_Comp2
Pressure 
R 
40416 
0 
SAF/EAF Pressure 
and Flow 
Pressure compensation at breakpoint 2 
VentSettings.Cor_Comp2
Temp 
R 
40417 
10 
SAF/EAF Pressure 
and Flow 
Outdoor temp breakpoint 2 (must be 
higher than breakpoint 1 temp) 
VentSettings.Cor_Humidi
tyMaxDiff 
R 
40418 
10 % RH 
Humidity 
Max allowed difference between 
setpoint and humidity in room before 
alarm 
VentSettings.Cor_Humidi
tyStartLimit 
R 
40419 
15 % RH 
Humidity 
Start limit in % to start digital output 
signal "Cor_HumidityStart(0)" 
VentSettings.Cor_Humidi
tyStopLimit 
R 
40420 
5 % RH 
Humidity 
Stop limit in % to stop digital output 
signal "Cor_HumidityStart(0)" 
VentSettings.Cor_Humidi
tyAutoMode 
X 
40421 
2 
Manual/Auto 
Running mode humidity start signal 
0=Off 
1=On 
2=Auto 
VentSettings.Cor_ExchSt
artDelay 
I 
40422 
0 s 
Settings, General 
Start delay Exchanger (s) 
VentSettings.Cor_DXBlo
ckLimit 
R 
40423 
0°C 
Settings, General 
If lower outdoor temperature all steps 
for DX-cooling is blocked 
VentSettings.Cor_SAFFu
llspeedOutput 
R 
40424 
75 % 
SAF/EAF Pressure 
and Flow 
Output signal (0...100 %) full speed 
SAF if Frequency control manually 
VentSettings.Cor_SAFHa
lfspeedOutput 
R 
40425 
50 % 
SAF/EAF Pressure 
and Flow 
Output signal (0...100 %) half speed 
SAF if Frequency control manually 
VentSettings.Cor_EAFFu
llspeedOutput 
R 
40426 
75 % 
SAF/EAF Pressure 
and Flow 
Output signal (0...100 %) full speed 
EAF if Frequency control manually 
VentSettings.Cor_EAFHa
lfspeedOutput 
R 
40427 
50 % 
SAF/EAF Pressure 
and Flow 
Output signal (0...100 %) half speed 
EAF if Frequency control manually 
VentSettings.Cor_CoolSt
epBlock1 
R 
40428 
0 % 
Settings, General 
If frequens output signal SAF is lower 
cool step 1 is blocked 
VentSettings.Cor_CoolSt
epBlock2 
R 
40429 
0 % 
Settings, General 
If frequens output signal SAF is lower 
cool step 2 is blocked 
VentSettings.Cor_CoolSt
epBlock3 
R 
40430 
0 % 
Settings, General 
If frequens output signal SAF is lower 
cool step 3 is blocked 
VentSettings.Cor_CoolSt
epBlockLimit1(0) 
R 
40431 
13°C 
Settings, General 
If lower outdoor temperature 
Cool step 1 is blocked 
VentSettings.Cor_CoolSt
epBlockLimit2 
R 
40432 
13°C 
Settings, General 
If lower outdoor temperature 
Cool step 2 is blocked 
VentSettings.Cor_CoolSt
epBlockLimit3 
R 
40433 
13°C 
Settings, General 
If lower outdoor temperature 
Cool step 3 is blocked 
VentSettings.Cor_ExtraU
nitFunc 
X 
40434 
0 
Extra Unit 
Start/Stop function Extra Unit: 
0=Off 
1=Always running 
2=Running if unit is running 