Chapter 5 Holding Register  51 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
TimePro.TimeGroupStatu
sCor_ExtraTimeGroup5 
X 
40399 
4 
Manual/Auto 
Manual/Auto Timer output 5: 
Modbus: 
0=Manual-Off 
1=Manual-On 
2=Forced Off 
3=Forced On 
4=Auto 
BACnet: 
1=Manual-Off 
2=Manual-On 
3=Forced Off 
4=Forced On 
5=Auto 
Alarms.AlaAcknow 
X 
40400 
255 
Alarm 
Acknowledging, 
Blocking and 
Unblocking 
External alarm acknowledge by setting 
this signal to the alarm number that 
should be acknowledge. 
Alarms.AlaBlock 
X 
40401 
255 
Alarm 
Acknowledging, 
Blocking and 
Unblocking 
External alarm blocking by setting this 
signal to the alarm number that should 
be blocked. 
Alarms.AlaUnBlock 
X 
40402 
255 
Alarm 
Acknowledging, 
Blocking and 
Unblocking 
External alarm unblocking by setting 
this signal to the alarm number that 
should be unblocked. 
VentSettings.Cor_HeatPu
mpLimit 
R 
40403 
10°C 
Actual/Setpoint 
If lower outdoor temp the heating pump 
is not stopped 
VentSettings.Cor_Supply
SetpointMax 
R 
40404 
30°C 
Supply, Extract and 
Room temperatures 
Max limit of supply setpoint when 
cascade control 
VentSettings.Cor_Supply
SetpointMin 
R 
40405 
12°C 
Supply, Extract and 
Room temperatures 
Min limit of supply setpoint when 
cascade control 
QSystem.Sec 
X 
40406 
Real Time Clock 
Real time clock: Second 0-59 
QSystem.Minute 
X 
40407 
Real Time Clock 
Real time clock: Minute 0-59 
QSystem.Hour 
X 
40408 
Real Time Clock 
Real time clock: Hour 0-23 
QSystem.WDay 
X 
40409 
Real Time Clock 
Real time clock: Day of Week 1-7, 
1=Monday 
QSystem.Week 
X 
40410 
Real Time Clock 
Real time clock: Week number 1-53 
QSystem.Date 
X 
40411 
Real Time Clock 
Real time clock: Day of month 1-31 
QSystem.Month 
X 
40412 
Real Time Clock 
Real time clock: Month 1-12 
QSystem.Year 
X 
40413 
Real Time Clock 
Real time clock: Year 0-99 
VentSettings.Cor_Comp1
Pressure 
R 
40414 
0 
SAF/EAF Pressure 
and Flow 
Pressure compensation at breakpoint 1 
VentSettings. 
Cor_Comp1Temp 
R 
40415 
-20 
SAF/EAF Pressure 
and Flow 
Outdoor temp breakpoint 1 (must be 
lower than breakpoint 2 temp) 