CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
50    Chapter 5 Holding Register 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
TimePro.TimeGroupStatu
sFanFullSpeed 
X 
40393 
4 
Manual/Auto 
Manual/Auto Full Speed time channel: 
Modbus: 
0=Manual-Off 
1=Manual-On 
2=Forced Off 
3=Forced On 
4=Auto 
BACnet: 
1=Manual-Off 
2=Manual-On 
3=Forced Off 
4=Forced On 
5=Auto 
TimePro.TimeGroupStatu
sFanHalfSpeed 
X 
40394 
4 
Manual/Auto 
Manual/Auto Half Speed time channel: 
Modbus: 
0=Manual-Off 
1=Manual-On 
2=Forced Off 
3=Forced On 
4=Auto 
BACnet: 
1=Manual-Off 
2=Manual-On 
3=Forced Off 
4=Forced On 
5=Auto 
TimePro.TimeGroupStatu
sCor_ExtraTimeGroup1 
X 
40395 
4 
Manual/Auto 
Manual/Auto Timer output 1: 
0=Manual-Off 
1=Manual-On 
2=Forced Off 
3=Forced On 
4=Auto 
TimePro.TimeGroupStatu
sCor_ExtraTimeGroup2 
X 
40396 
4 
Manual/Auto 
Manual/Auto Timer output 2: 
0=Manual-Off 
1=Manual-On 
2=Forced Off 
3=Forced On 
4=Auto 
TimePro.TimeGroupStatu
sCor_ExtraTimeGroup3 
X 
40397 
4 
Manual/Auto 
Manual/Auto Timer output 3: 
0=Manual-Off 
1=Manual-On 
2=Forced Off 
3=Forced On 
4=Auto 
TimePro.TimeGroupStatu
sCor_ExtraTimeGroup4 
X 
40398 
4 
Manual/Auto 
Manual/Auto Timer output 4: 
0=Manual-Off 
1=Manual-On 
2=Forced Off 
3=Forced On 
4=Auto 