CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 1  Corrigo with EXOline, Modbus and BACnet communication  5 
Baudrate 
150, 300, 600, 1200, 2400, 4800, 9600 
BACnet communication 
Corrigo  is  capable  of  communication  via  the  BACnet-AAC  (Advanced  Application  Controller) 
protocol, using either IP or MS/TP data link formats. A B-AAC unit is a device that may be intended 
for a specific application, but which supports some degree of programmability allows the user to do 
more – such as generate alarms, definine schedules, synchronize clocks, etc.  
In  order  to  connect a  Corrigo  running  a  ventilation  application to  a  BAS  (Building  Automation 
System) via BACnet/IP, a third generation Corrigo with a TCP/IP port is required. To connect to a 
BAS via BACnet MS/TP, a third generation Corrigo with an RS485 communication port is required. 
With the default install path entered upon software installation, BACnet objects lists will be located 
in the following directory: 
C:\Program Files\EXO\SLib\Corrigo\VentilationProgram3_6\BACnet 
The lists can also be found in E tool
©
, under the menu “Help”. 
BACnet type 
The BACnet type of signals: 
10XXX = Read and write binary 
20XXX = Read binary 
30XXX = Read and write analogue 
40XXX = Read analogue 
30XXX = Read and write multistate 
40XXX = Read multistate 
(Where XXX = Modbus address) 
NOTE: In the variable lists contained in this manual, the following abbrevations are used: 
AV = Analogue Value 
BV = Binary Value 
MSV = Multistate Value 
BACnet object names are the same as for EXOL type objects, but are shortened by removing the 
preamble “Cor_” (e.g.: “VentSettings.Cor_OverHeatFastStop” becomes 
“VentSettings.OverHeatFastStop”, etc.). 
BACnet/IP configuration 
Upon delivery, the BACnet/IP protocol is disabled as a default. To enable BACnet communication, 
simply change the setting “Not active” to “Active”. The  protocol will now be available for use: 
TCP/IP  
BACnet/IP 
communication 
Active  










