CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 4  Input Register  27 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
InputOutput.Exp2AnaOut4 
R 
30246 
Analogue 
outputs 
Value of AO4 Exp. Unit 2 
InputOutput.Exp2AnaOut5 
R 
30247 
Analogue 
outputs 
Value of AO5 Exp. Unit 2 
VentSettings.Cor_ExpAo(0) 
X 
30248 
Analogue 
outputs 
Connected signal on AO1 Exp. Unit 
1: 
0=Not used 
1=Y1-Heating 
2=Y2-Exchanger 
3=Y3-Cooling 
4=SAF 
5=EAF 
6=Y6-Humidity 
7=Split of Y1, Y2 or Y3 
8=Extra unit 
9=Heat/Cool (change over) 
10=Extra sequence Y4 
VentSettings.Cor_ExpAo(1) 
X 
30249 
Analogue 
outputs 
Connected signal on AO2 Exp. Unit 
1: 
(See signal list for AO1) 
VentSettings.Cor_ExpAo(2) 
X 
30250 
Analogue 
outputs 
Connected signal on AO3 Exp. Unit 
1: 
(See signal list for AO1) 
VentSettings.Cor_ExpAo(3) 
X 
30251 
Analogue 
outputs 
Connected signal on AO4 Exp. Unit 
1: 
(See signal list for AO1) 
VentSettings.Cor_ExpAo(4) 
X 
30252 
Analogue 
outputs 
Connected signal on AO5 Exp. Unit 
1: 
(See signal list for AO1) 
VentSettings.Cor_ExpAo(5) 
X 
30253 
Analogue 
outputs 
Connected signal on AO1 Exp. Unit 
2: 
(See signal list for AO1) 
VentSettings.Cor_ExpAo(6) 
X 
30254 
Analogue 
outputs 
Connected signal on AO2 Exp. Unit 
2: 
(See signal list for AO1) 
VentSettings.Cor_ExpAo(7) 
X 
30255 
Analogue 
outputs 
Connected signal on AO3 Exp. Unit 
2: 
(See signal list for AO1) 
VentSettings.Cor_ExpAo(8) 
X 
30256 
Analogue 
outputs 
Connected signal on AO4 Exp. Unit 
2: 
(See signal list for AO1) 
VentSettings.Cor_ExpAo(9) 
X 
30257 
Analogue 
outputs 
Connected signal on AO5 Exp. Unit 
2: 
(See signal list for AO1) 