CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
Chapter 4  Input Register  25 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_ExpDi(0) 
X 
30214 
Digital inputs 
Connected signal on DI1 Exp. Unit 1: 
0=Not used 
1=SAF-Ind 
2=EAF-Ind 
3=P1-Heating 
4=P1-Exchanger 
5=P1-Cooling 
6=Filter guard 
7=Fire alarm 
8=Fire damper-ind 
9=Ext run 1/1 
10=Ext run ½ 
11=External alarm 
12=External switch 
13=Flow guard 
14=Rot.sent.exch 
15=De-icing 
16=Frostprotection 
17=Overheatprotection 
18=Recirculation run 
19=Change over 
20=Filter guard 2 
VentSettings.Cor_ExpDi(1) 
X 
30215 
Digital inputs 
Connected signal on DI2 Exp. Unit 1: 
(See signal list for DI1) 
VentSettings.Cor_ExpDi(2) 
X 
30216 
Digital inputs 
Connected signal on DI3 Exp. Unit 1: 
(See signal list for DI1) 
VentSettings.Cor_ExpDi(3) 
X 
30217 
Digital inputs 
Connected signal on DI4 Exp. Unit 1: 
(See signal list for DI1) 
VentSettings.Cor_ExpDi(4) 
X 
30218 
Digital inputs 
Connected signal on DI5 Exp. Unit 1: 
(See signal list for DI1) 
VentSettings.Cor_ExpDi(5) 
X 
30219 
Digital inputs 
Connected signal on DI6 Exp. Unit 1: 
(See signal list for DI1) 
VentSettings.Cor_ExpDi(6) 
X 
30220 
Digital inputs 
Connected signal on DI7 Exp. Unit 1: 
(See signal list for DI1) 
VentSettings.Cor_ExpDi(7) 
X 
30221 
Digital inputs 
Connected signal on DI8 Exp. Unit 1: 
(See signal list for DI1) 
VentSettings.Cor_ExpDi(8) 
X 
30222 
Digital inputs 
Connected signal on UDI1 Exp. Unit 
1: 
(See signal list for DI1) 
VentSettings.Cor_ExpDi(9) 
X 
30223 
Digital inputs 
Connected signal on UDI2 Exp. Unit 
1: 
(See signal list for DI1) 
VentSettings.Cor_ExpDi(10) 
X 
30224 
Digital inputs 
Connected signal on UDI3 Exp. Unit 
1: 
(See signal list for DI1) 
VentSettings.Cor_ExpDi(11) 
X 
30225 
Digital inputs 
Connected signal on UDI4 Exp. Unit 
1: 
(See signal list for DI1) 