CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
18    Chapter 4 Input Register 
Signal name 
EXOL type
Modbus address
Default value
Function 
Description 
VentSettings.Cor_Ao2 
X 
30060 
Analogue 
outputs 
Connected signal on AO2: (See signal 
list for AO1) 
VentSettings.Cor_Ao3 
X 
30061 
Analogue 
outputs 
Connected signal on AO3: (See signal 
list for AO1) 
VentSettings.Cor_Ao4 
X 
30062 
Analogue 
outputs 
Connected signal on AO4: (See signal 
list for AO1) 
VentSettings.Cor_Ao5 
X 
30063 
Analogue 
outputs 
Connected signal on AO5: (See signal 
list for AO1) 
VentSettings.Cor_Do1(0) 
X 
30064 
Digital outputs 
Connected signal on DO1: 
0 = Not Used 
1 = SAFStart1 
2 = EAFStart1 
3 = SAFStart2 
4 = EAFStart2 
5 = HeatingPumpStart 
6 = ExchangerStart 
 7 = CoolingPumpStart 
8 = FireDamper 
9 = SumAlarm 
10 = SumAlarmA 
11 = SumAlarmB 
12 = SAFFrequencyStart 
13 = EAFFrequencyStart  
14 = HeatingActivate 
15 = ExchangerActivate 
16 = CoolingActivate 
17 = RecycleAirDamper 
18 = FreshAirDamper 
19 = ExtractAirDamper 
20 = HeatingIncrease 
21 = HeatingDecrease 
22 = ExchangerIncrease 
23 = ExchangerDecrease 
24 = CoolingIncrease 
25 = CoolingDecrease 
26 = HeatStep1 
27 = HeatStep2 
28 = HeatStep3 
29 = HeatStep4 
30 = CoolStep1 
31 = CoolStep2 
32 = CoolStep3 
33 = TimeChannel1 
34 = TimeChannel2 
35 = TimeChannel3 
36 = TimeChannel4 
37 = TimeChannel5 
38 = Humidity start 
39 = Extra unit start 
40 = Heat/Cool step 1 
41 = Heat/Cool step 2 
42 = Heat/Cool step 3 
43 = Night cool run 