CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
 - About Corrigo
 - Display, buttons and LEDs
 - The menu system
- Navigating the menus
 - Running mode
 - Temperature
- Setpoint Supply air temperature control
 - Setpoint Outdoor temperature compensated Supply air control
 - Setpoint Cascaded room temperature control
 - Setpoint Cascaded extract air temperature control
 - Setpoint Outdoor compensated room temperature/extract air control
 - Support control heating/Support control cooling
 - Frost protection temperature
 - Exchanger de-icing
 - Heat exchanger efficiency monitoring
 - Recirculation
 - Extra controller unit
 - Enthalpy control
 
 - Air control
- Pressure control SAF (there are also corresponding menus for EAF)
 - Flow control SAF (there are also corresponding menus for EAF)
 - Manual frequency control SAF (there are also corresponding menus for EAF)
 - Frequency control external
 - Frequency control SAF with EAF slave/flow control (also available for opposite function)
 - CO2
 
 - Humidity control
 - Time settings
 - Access rights
 
 - Other functions
 - Index
 
Corrigo ventilation user guide, revision F  The menu system    
17 
Submenu Extra compensation. A temperature 
dependent compensation similar to the one 
above but with selectable temperature source. 
Manual frequency control SAF (there are also corresponding menus for 
EAF) 
Here, Actual and Setpoint values are displayed. This is a read-
only menu. No settings can be made here. 
Submenu Setpoint values for normal speed (1/1) 
and reduced speed (1/2). 
The setpoint is set in % of the full output. 100 % 
= 10 V output signal. 
Submenu outdoor compensation. An outdoor 
temperature dependent compensation of the 
pressure setpoint value can be added.  
The compensation can be set for either the supply air fan alone or for both fans. 
Submenu extra compensation. A temperature 
dependent compensation similar to the one above 
but with selectable temperature source. 
Frequency control external 
For fan control using an external control signal, e.g. via a VAV 
optimizer. 
Comp sens:Room temp1 
15 °C = 0 m3/h 
20 °C = 0 m3/h 
25 °C = 0 m3/h 
Frequency control 
manual SAF 
Output: 75% 
Frequency control 
manual SAF 
Output 1/1: 75% 
Output 1/2: 50% 
Outdoor comp output 
 -20 °C = -40 % 
 10 °C = 0 % 
Act comp: 0 %  
Comp sens:Room temp1 
15 °C = 0 % 
20 °C = 0 % 
25 °C = 0 % 
Frequency Control 
manual SAF 
Output: 0 % 
Outdoor comp outp 
 -20 °C = -40 % 
 10 °C = 0 % 
Act comp: 0 %  
Comp sens:Room temp1 
15 °C = 0 % 
20 °C = 0 % 
25 °C = 0 % 