404559 KD OIPMFR ES
12
Wiring
120/230 Volt Single Phase Fan
KD 12XL-EF, KD 14-EF, KD 14XL-EF, KD 16-EF, KD 16XL-EF and
KD 18-EF
Wiring schematic for 4 lead motors, single phase
1. All leads are color coded as well as identied with
an Alpha/ Alpha or Alpha/Numeric code (i.e. TK or
Z2). This code may be shown as a band on the
wire or on a schematic on the motor hub. Colors
should be veried against code band. If code
band and color do not correspond to schematics
above, wire according to the code on the band.
2. Color of capacitor leads may be reversed. Fan
operation will not be affected.
208/230 Volt Three Phase Fans
1. Contactor should be used. Control coil should be
wired in series with motor thermal contacts (TK
leads) as shown in diagram to provide thermal
motor protection.
2. All leads are color coded as well as identied
with a band containing an Alpha/Alpha or Alpha/
Numeric code (i.e. TK or Z2). Colors should be
veried against code band. If code band and
color do not correspond to schematics above,
wire according to the code on the band.
460 Volt Three Phase Fan
For 460 volt operation, Orange (W2), Red (U2) and
Grey (V2) wires must be spliced together.
1. Contactor should be used. Control coil should be
wired in series with motor thermal contacts (TK
leads) as shown in diagram to provide thermal
motor protection.
2. All leads are color coded as well as identied
with a band containing an Alpha/Alpha or Alpha/
Numeric code (i.e. TK or Z2). Colors should be
veried against code band. If code band and
color do not correspond to schematics above,
wire according to the code on the band.
L1
Incoming
3-Phase Supply 208/230/460
Control Power
for Contactor
AC Contactor
L2 L3
TK TK L1 L2 L3 L3
Ground
T1 T2 T3
C1
C2
Motor Leads
Contactor for 3-Phase Fans, 208-230/460v